COMPRESSOR, WATER INLET SOLENOID VALVE, HOT GAS VALVE

NOTE: The length of the defrost cycle is (non-adjustable) automatically determined by the microprocessor of The P.C. BOARD in relation to

the time T2 necessary for the unit to reduce the evaporator temperature from 0˚C (35˚F) to -1 3˚C (8.5˚F) and of the ambient temperature, as

illustrated in Table C.

As shown it is possible to have a different length of the defrost cycle in connection with the different length of the second phase of the freezing

cycle T2 relative to the ambient temperature situations; shorter when the ambient temperature is high and longer in colder ambients so to

partially compensate the length of the freezing cycle, which is longer in high ambient temperatures and shorter in low ones.

H.

Check, during the defrost cycle, that the incoming water flows correctly into the sump reservoir in order to refill it and that its surplus overflows

through the overflow drain tube.

I.

Check the texture of ice cubes just released. They have to be the right shape with a small depression of about 5-6mm in their crown.

If not, wait for the completion of the second cycle before performing any adjustment.

If the ice cubes require a correction to their shape, it is possible to modity the length of the timed freezing cycle by changing the

DIP SWITCH

keys setting as illustrated in table B.

It the ice cubes are shallow and cloudy, it is possible that the ice maker runs short of water during the freezing cycle second phase or, the quality

of the supplied water requires the use of an appropriate water filter or conditioner or the installation of the optional water drain valve kit KWD.

J.

To be sure of the correct operation of the ice level temperature sensor, located in one side of storage bin liner, during the defrost cycle place

one shovel of ice cubes in contact with its probe for approx. 30 sec.-1 minute.

As the temperature of storage bin sensor reaches the value of +2˚C (35˚F), the ice level control transmits a signal to the microprocessor of the

P.C. BOARD in order to stop the ice maker operation at the end of the defrost cycle with the simultaneous glowing of the

3rd RED LIGHT, to

monitor the

BIN FULL situation (Fig.6). Page 13

With no more ice cubes in touch with the ice level control the temperature of its probe progressively rises to reach + 4.5˚C (40˚F) and at this

point the ice machine restarts to initiate a new freezing cycle with the simultaneous extinguishing of the

3rd RED LIGHT.

NOTE The CUT-IN RANGE OF THE ICE LEVEL CONTROL SENSOR can be adjusted as shown in table D; its cut out setting remains however

at + 2˚C (35˚F).

6.

Principle of Operation

6.1 How it works

In the cube ice makers the water used to make the ice is kept constantly in circulation by an electric water pump which primes it to the spray

system nozzles from where it is diverted into the inverted mould cups of the evaporator. A small quantity of the sprayed water freezes into ice;

the rest of it cascades by gravity into the sump assembly below for recirculation.

6.2 Freezing Cycle

The hot gas refrigerant discharged out from the compressor reaches the condenser where, being cooled down, condenses into liquid. Flowing

into the liquid line it passes through the drier filter, then it goes all the way through the capillary tube where, due to the heat exchanging action,

it loses some of its heat content so that its pressure and temperature are lowered as well.

Next the refrigerant enters into the evaporator serpentine (which has a larger l.D. than the capillary) and starts to boil off; this reaction is

emphasised by the heat transferred by the sprayed water.

The refrigerant then increases in volume and changes entirely into vapour.

The vapour refrigerant then passes through the suction accumulator (used to prevent any small amount of liquid refrigerant reaching the

compressor) and through the suction line. In both the accumulator and the suction line it exchanges heat with the refrigerant flowing into the

capillary tube (warmer), before being sucked into the compressor and recirculated as hot compressed refrigerant gas.

The freezing cycle is controlled by the evaporator temperature sensor (which has its probe in contact with the evaporator serpentine) which

determines the length of the first and second portion of it and it is signalled by the glowing of the

6th RED LED.

The first portion length or time

T1 (non-adjustable) is equal to the time required by the temperature sensor to fall to 0˚C (35˚F). When reached,

it is signalled by the glowing of the

5th RED LED.

NOTE If, after 15 minutes, the evaporator temperature has not yet reached the value of 0˚C (35˚F) (due to a partially or total shortage of

refrigerant or to a too high condensing temperature, etc.) the sensor, through the P.C. BOARD, causes the unit to stop the operation with the

simultaneous glowing of the

SECOND RED WARNING LED (Fig. 7). Page 13. After having eliminated the source of the unit trip off, to restart

the machine operation it is necessary first to rotate the program selector to the

RE-SET position, then put it again on to OPERATION position

or, alternatively, switch OFF and ON the unit at the power line Main Switch.

The

second portion length of freezing cycle or time T2 (non-adjustable) is equal to the time required by the evaporator temperature to go from

0˚C (35˚F) to -13˚C (8.5˚F) on models 20, 30, 40 and 60 or to -16˚C (3˚F) on model 85. The sensor will light-up the 4th RED LED.

NOTE In case the time T2 gets longer than 45 minutes, the unit stops with the glowing of the second RED WARNING LED.

Also in this case, after having eliminated the source of the trip OFF to restart the machine it is necessary first to rotate the program selector to

the

RESET position then put it again on OPERATION or, switch OFF and ON the unit at power line Main Switch.

The

third portion or time Ta (added time) of the freezing cycle is controlled by the electronic timer of P.C. BOARD. As the evaporator temperature

reaches the value of

-13˚C (8.5˚F) or to -16˚C (3˚F); the sensing probe of the evaporator sensor (in contact with the serpentine) changes its

electrical resistance causing a low voltage current to flow to the P.C. BOARD which, thereby, activates an

electronic timer.

NOTE The activation of the timer (Time mode) of P.C. BOARD is signalled by the glowing of fourth RED LED located in the front of the P.C.

BOARD.

ATTENTION In case the length of the second portion of freezing cycle or time T2, lasts as long as between 35 and 45 minutes, the

third portion or time Ta gets skipped by the P.C BOARD which puts the unit directly in the defrost or harvest cycle.

The length of the third portion of the freezing cycle (adjustable) is pre-fixed and related to the setting of the

DIP SWITCH keys 3, 4, 5, 6 and

9

11. Principle of Operation

11.1 How it works

In the cube ice makers the water used to make the ice is kept constantly in circulation by an electric water pump which primes it to the spray

system nozzles from where it is diverted into the inverted mould cups of the evaporator. A small quantity of the sprayed water freezes into ice;

the rest of it cascades by gravity into the sump assembly below for recirculation.

11.2 Freezing Cycle

The Hot refrigerant gas discharged out from the compressor reaches the condenser where, being cooled down, condenses into liquid. Flowing

into the liquid line it passes through the drier filter, then it goes all the way through the capillary tube where, due to the heat exchanging action,

it loses some of its heat content so that its pressure and temperature are lowered as well.

Next the refrigerant enters into the evaporator serpentine (which has a larger I.D. then the capillary) and starts to boil off; this reaction is

emphasized by the heat transferred by the sprayed water.

The refrigerant then increases in volume and changes entirely into vapour.

The refrigerant vapour then passes through the suction accumulator (used to prevent any small amount of liquid refrigerant from reaching the

compressor) and through the suction line. In both the accumulator and the suction line it exchanges heat with the refrigerant flowing into the

capillary tube (warmer), before being sucked in the compressor and to be recirculated as high pressure, high temperature gas.

The freezing cycle is controlled by the evaporator temperature sensor (which has its probe in contact with the evaporator serpentine) that

determines the length of the cycle first portion.

When the temperature of the evaporator serpentine drops to a pre-set value, the evaporator sensor probe changes its electrical resistance

allowing a low voltage current (8-10 volts) to flow to the P.C. BOARD which in turn activates an electronic timer.

The timer, which is built-in the P.C. BOARD, takes over, from the evaporator temperature sensor, the control of the freezing cycle up to its

completion.

NOTE: The change of the electrical potential of the evaporator sensor with the consequent activation of the timer (Time mode) is signalled by

the glowing-up of the

RED LED located in the front of the P.C. BOARD.

ATTENTION: In case, after 15 minutes from the beginning of the freezing cycle, the temperature of the evaporator sensor probe is higher then

0°C (32°F) (Shortage of refrigerant, inoperative hot gas valve, etc.) the P.C. BOARD switch OFF immediately the unit with the simultaneous

blinking of the WARNING RED LED.

The length of the second portion of the freezing cycle is pre-fixed and related to the setting of the first four DIP SWITCH keys which is made in

relation with the different unit versions.

The DIP SWITCH keys setting is made in consideration of the type of condenser used.

In Table B, page 18, are indicated the various lengths of the second portion of freezing cycle (Time mode) in relation to the different combinations

of the DIP SWITCH KEYS.

In Table A, page 18, is illustrated the DIP SWITCH keys combinations for the different unit versions as they are set in the factory.

The electrical components in operation during the freezing cycle are:

COMPRESSOR

FAN MOTOR (in air cooled version)

WATER PUMP

CONTACTOR COIL

and during the second phase of freezing cycle (Time mode) they are joined by the

ELECTRONIC TIMER

The refrigerant head pressure, in the course of the freezing cycle, ranges between 13.5 and 14.5 bars (190-205 psig) being controlled by the

temperature sensor probe located within the condenser fins (Air cooled version) or, it is kept constant at 14 bars (195 psig) by means of the

water regulating valve (water cooled version).

On the air cooled version, the condenser temperature sensor, when senses a rising of the condenser temperature beyond the pre-fixed limit,

changes its electrical resistance and send a low voltage power signal to the Micro Processor of P.C. BOARD which in turn energizes, through

a

TRIAC, the FAN MOTOR.

When the opposite situation occurs, i.e. the condenser temperature gets below the pre-fixed limit, the temperature sensor changes again its

electrical resistance reducing therefore the current flow to the P.C. BOARD to cause the fan motor to temporary cut-off.

NOTE: In case the condensor temperature probe senses that the condensor temperature has rised to 70°C (160°F) - on air cooled versions

- or 62°C (145°F) - on water cooled versions - for one of the following abnormal reasons:

CLOGGED CONDENSOR (Air cooled version)

FAN MOTOR OUT OF OPERATION (Air cooled version)

INSUFFICIENT FLOW OF COOLING WATER (Water cooled version)

AMBIENT TEMPERATURE HIGHER THEN 40°C (100°F)

it causes the total and immediate SHUT-OFF of the machine in order to prevent the unit from operating in abnormal and dangerous conditions.

When the ice maker stops on account of this protective device, there is a simultaneous glowing of the

RED LED, warning the user of the Hi

Temperature situation. After having eliminated the source of the condensor hi-temperature, to restart the machine it is necessary first, to rotate

for a while the program selector on

RE-SET position then, to rotate it again on OPERATION position.

The same can be done by just switching OFF and ON the unit at main line switch.

The ice machcine resumes its normal operation by going through the 5 minutes water filling phase.

At the start of the freezing cycle the refrigerant suction or lo-pressure lowers rapidly to 3.3 bar-45 psig then it declines gradually - in relation

with the growing of the ice thickness - to reach, at the end of the cycle, approx. 1 bar -14 psig with the cubes fully formed in the cup moulds.

The total length of the freezing cycle ranges from 15-18 minutes.

11.3 Defrost or Harvest Cycle

As the electronic timer has carried the system throughout the second phase of freezing cycle, the defrost cycle starts.

ATTENTION: In case the unit is be able to reach 0°C (32°F) evaporating temperature within 15 minutes, or after 45 minutes from the beginning

of the freezing cycle it has not yet reached the evaporator temperature of -15°C (5°F), the machine goes straight into the defrost cycle omitting

the timed portion of the freezing cycle related to the setting of the first four DIP SWITCHES.

NOTE: The length of the defrost cycle is pre-determined by the setting of the DIP SWITCH KEYS NO. 5, 6 and 7 and it is related as well to the