Through-the-wall installations, Before after, Top view – Friedrich KS15 User Manual

Page 15

Advertising
background image

15

920-198-00

STEP 1 Follow steps 1, 2, 3 and 4 of the "STANDARD SASH WINDOW

INSTALLATION" instructions beginning on page 10.

STEP 2 CABINET PREPARATION – Remove the sill plate from the

cabinet by removing the two nuts and screws re tain ing the sill
plate. Note that the chassis retainer is secured by a right side
nut and screw (See Detail 1, Figure A.) Bend the tabs of the
sill plate down into its channel at both ends of the plate or cut
them off (See Detail 2, Figure A.) Turn the sill plate end to end,
180° and reinstall. Reverse the ori en ta tion of nuts and screws
so that the head of screw is on bottom of cabinet facing up and
nut is on top facing down (See Detail 3, Figure A.) Insure that
the chassis retainer is reinstalled as shown in the detail.

Figure A

BEFORE

AFTER

CABINET

SILL

PLATE

TURN SILL PLATE
END TO END

SCREW
(2 REQUIRED)

NOTE: HOLES
MOVED TO
BACK SIDE

NUT
(2 REQUIRED)

RETAINER, CHASSIS
THIS SIDE ONLY

DETAIL 1

BEND TABS DOWN

DETAIL 2

DETAIL 3

SCREW
(2 REQUIRED)

SCREW AND NUT

ORIENTATION NOW

REVERSED

NUT
(2 REQUIRED)

STEP 3 WALL PREPARATION – The maximum wall thickness permis-

sible without special construction is de ter mined by the model size
to be installed. THE OUTSIDE CABINET CONDENSER-AIR-
INTAKE-LOU VERS MUST NOT BE BLOCKED BY EXTENDING
INSIDE THE WALL AREA. Observe the maximum wall thickness
shown in the chart and di a gram in Figure B.

SPECIAL INSTRUCTIONS FOR EXTRA THICK WALLS –
For installation in walls exceeding the max i mum thickness shown
in the chart, the following suggested construction may apply.

2" MINIMUM
BOTH SIDES

CONDENSER AIR
INTAKE LOUVERS

MAXIMUM WALL THICKNESS

CONDENSER
AIR INTAKE
LOUVERS

TOP VIEW SHOW ING
BEVELED SIDES FOR
AIR INTAKE. WALL
BELOW UNIT MUST BE
BEVELED ALSO.

TOP VIEW

CONDITIONED ROOM SIDE AIR

CONDENSER AIR

OUTLET / REJECTED

HEATED AIR

NOTE: Condenser air inlets
and outlet must be unobstruct-
ed to avoid the recirculation of
rejected heated air.

MODEL

A

SMALL CHASSIS

7 ⅜"

MEDIUM CHASSIS

7 ⅜"

LARGE CHASSIS

15 ⅛"

Through-the-wall Installations

The following instructions apply to wood, masonry, brick, concrete or cinder block wall con struc tion

Figure B EXTRA THICK WALL CON STRUC TION