Specifications – Fluke 430 Series User Manual

Page 4

Advertising
background image

Specifications

Input characteristics

Voltage inputs

Number of inputs

4 (3 phases + neutral)

Maximum input voltage

1000 Vrms

Maximum peak voltage

6 kV

Input impedance

4 M

Ω / 5 pF

Bandwidth

9 kHz, up to 100 kHz for transient display

Scaling

1:1, 10:1, 100:1, 1000:1 and variable

Current inputs

Number of inputs

4 (3 phases + neutral)

Type

Clamp on current transformer with mV output

Range

1 to 400 Arms with included clamps (I400S)
0.1 to 3000 Arms with optional clamps

Input impedance

50 k

Bandwidth

9 kHz

Scaling

0.1, 1, 10, 100, 1000 mV/A and variable

Nominal frequency

40 to 70 Hz

Sampling system

Resolution

16 bit analog to digital converter on 8 channels

Maximum sampling speed

200 kS/s on each channel simultaneously

RMS sampling

5000 samples on 10/12

2

cycles according IEC 61000-4-30

PLL synchronization

4096 samples on 10/12

2

cycles according IEC 61000-4-7

Display modes

Waveform display

Available in Scope and Transient mode
Captures 8 waveforms simultaneously
Display update rate 5 x per second
Up to 10/12 times horizontal zoom

2

Cursors: Single vertical line showing min, max, avg reading at cursor position

Phasor

Shows real time phasor diagram
Available in Scope and Unbalance mode
Display update rate 5 x per second

Matrix readings

Available in Volts/Amps/Hertz, Harmonics, Power & Energy, Flicker and Unbalance mode

AutoTrend graph

Available in Volts/Amps/Hertz, Dips & Swells, Harmonics, Power & Energy, Flicker,
Unbalance, Inrush and Monitor mode
Cursors: single vertical line showing with min, max, avg reading at cursor position

Bargraph

Available in Harmonics and Monitor mode

Eventlist

Available in Dips & Swells and Monitor mode

Measurement modes

Scope

Vrms, Arms, Vcursor, Acursor, Vfund, Afund, Hz, V phase angles, A phase angles

Volts/Amps/Hertz

Vrms, Vpk, V Crest Factor, Arms, Apk, A Crest Factor, Hz

Dips and Swells

Vrms

1

2

, Arms

1

2

Captures up to 1000 events with date, time, duration, magnitude and phase identification
with programmable thresholds

Harmonics DC, 1 to 50

Harmonic Volts, THD Volt, Harmonic Amps, THD Amps, K Amps, Harmonic Watts, THD
Watts, K Watts, Interharmonic Volts

4

, Interharmonic Amps

4

(relative to fundamental or to total rms)

Power and Energy

4

Watts, VA, VAR, Power factor, Cos

ϕ / DPF, Arms, Vrms, kWh, kVAh, KVARh, peak demand

interval using trend, KYZ revenue meter verification via optional input

Flicker

Pst(

1min

), Pst, Plt, PF5, Vrms

1

2

, Arms

1

2

, Dc, Dmax, TDEX

Unbalance

Vneg, Vzero, Aneg, Azero, Vfund, Afund, Hz, V phase angles, A phase angles

Transients

4

Vrms, Arms, Vcursor, Acursor

Inrush Currents

4

Inrush Current, Inrush duration, Arms

1

2

, Vrms

1

2

System Monitor

Vrms, Arms, Harmonic Volts, THD Volts, Plt, Vrms

1

2

, Arms

1

2

, Vneg, Hz, dips and swells,

unbalance. All parameters are measured simultaneously in accordance with EN50160.
Using Flagging to indicate unreliable readings according IEC61000-4-30.

4

Fluke Corporation Fluke 430 Series Three-Phase Power Quality Analyzers