Specifications – Fluke 430 Series User Manual
Page 4

Specifications
Input characteristics
Voltage inputs
Number of inputs
4 (3 phases + neutral)
Maximum input voltage
1000 Vrms
Maximum peak voltage
6 kV
Input impedance
4 M
Ω / 5 pF
Bandwidth
9 kHz, up to 100 kHz for transient display
Scaling
1:1, 10:1, 100:1, 1000:1 and variable
Current inputs
Number of inputs
4 (3 phases + neutral)
Type
Clamp on current transformer with mV output
Range
1 to 400 Arms with included clamps (I400S)
0.1 to 3000 Arms with optional clamps
Input impedance
50 k
Ω
Bandwidth
9 kHz
Scaling
0.1, 1, 10, 100, 1000 mV/A and variable
Nominal frequency
40 to 70 Hz
Sampling system
Resolution
16 bit analog to digital converter on 8 channels
Maximum sampling speed
200 kS/s on each channel simultaneously
RMS sampling
5000 samples on 10/12
2
cycles according IEC 61000-4-30
PLL synchronization
4096 samples on 10/12
2
cycles according IEC 61000-4-7
Display modes
Waveform display
Available in Scope and Transient mode
Captures 8 waveforms simultaneously
Display update rate 5 x per second
Up to 10/12 times horizontal zoom
2
Cursors: Single vertical line showing min, max, avg reading at cursor position
Phasor
Shows real time phasor diagram
Available in Scope and Unbalance mode
Display update rate 5 x per second
Matrix readings
Available in Volts/Amps/Hertz, Harmonics, Power & Energy, Flicker and Unbalance mode
AutoTrend graph
Available in Volts/Amps/Hertz, Dips & Swells, Harmonics, Power & Energy, Flicker,
Unbalance, Inrush and Monitor mode
Cursors: single vertical line showing with min, max, avg reading at cursor position
Bargraph
Available in Harmonics and Monitor mode
Eventlist
Available in Dips & Swells and Monitor mode
Measurement modes
Scope
Vrms, Arms, Vcursor, Acursor, Vfund, Afund, Hz, V phase angles, A phase angles
Volts/Amps/Hertz
Vrms, Vpk, V Crest Factor, Arms, Apk, A Crest Factor, Hz
Dips and Swells
Vrms
1
⁄
2
, Arms
1
⁄
2
Captures up to 1000 events with date, time, duration, magnitude and phase identification
with programmable thresholds
Harmonics DC, 1 to 50
Harmonic Volts, THD Volt, Harmonic Amps, THD Amps, K Amps, Harmonic Watts, THD
Watts, K Watts, Interharmonic Volts
4
, Interharmonic Amps
4
(relative to fundamental or to total rms)
Power and Energy
4
Watts, VA, VAR, Power factor, Cos
ϕ / DPF, Arms, Vrms, kWh, kVAh, KVARh, peak demand
interval using trend, KYZ revenue meter verification via optional input
Flicker
Pst(
1min
), Pst, Plt, PF5, Vrms
1
⁄
2
, Arms
1
⁄
2
, Dc, Dmax, TDEX
Unbalance
Vneg, Vzero, Aneg, Azero, Vfund, Afund, Hz, V phase angles, A phase angles
Transients
4
Vrms, Arms, Vcursor, Acursor
Inrush Currents
4
Inrush Current, Inrush duration, Arms
1
⁄
2
, Vrms
1
⁄
2
System Monitor
Vrms, Arms, Harmonic Volts, THD Volts, Plt, Vrms
1
⁄
2
, Arms
1
⁄
2
, Vneg, Hz, dips and swells,
unbalance. All parameters are measured simultaneously in accordance with EN50160.
Using Flagging to indicate unreliable readings according IEC61000-4-30.
4
Fluke Corporation Fluke 430 Series Three-Phase Power Quality Analyzers