Specifications

continued

Accuracy, resolution and range

Volt/Amps/Hertz

Measurement range

Resolution

Accuracy

Vrms (AC+DC)

1 to 1000 Vrms

0.1 Vrms

± 0.5 % of nominal voltage

Vpk

1 to 1400 Vpk

1 V

5 % of nominal voltage

CFV

1.0 to > 2.8

0.1

± 5 %

Arms (AC+DC)

0 to 20,000 Arms

1

0,001 to 10 Arms

1

± 1 % of reading ± 5 counts

3

with included clamps

0 to 400 Arms

0.1 and 1 Arms

Apk

using 1mV/A scaling

0 - 5500 Apk

10 A

± 5 %

CFA

using 1mV/A scaling

1 to 10

0.1

± 5 %

50 Hz nominal

42.50 to 57.50 Hz

0.01 Hz

± 0.1 % of nominal frequency

60 Hz nominal

51.00 to 69.00 Hz

0.01 Hz

± 0.1 % of nominal frequency

Dips and swells

Vrms

1

2

(AC+DC)

0.0 to100 % of nominal voltage

0.1Vrms

± 1 % of nominal voltage

Arms

1

2

(AC+DC)

0 to 20,000 Arms

1

0,001 Arms to 10 Arms

± 1 % of reading ± 5 counts

3

with included clamps

0 to 400 Arms

0.1 Arms and 1 Arms

Threshold levels

Programmable in percent of nominal voltage

Duration

hhh,mm,ss,mmm with half-cycle cycle time resolution

Harmonics

Harmonic selection (n)

DC, 1 to 50

Inter-Harmonic selection

Off, 1 to 49

Vrms

Relative (%f):

0.0 to 100.0 %

0.1 %

± 0.1 % ± n x 0.1 %
(± 0.4 % for %r)

Absolute:

0.0 to 1000 Vrms

0.1 Vrms

± 5 % of reading ± 2 counts

Arms

Relative (%f):

0.0 to 100.0 %

0.1 %

± 0.1 % ± n x 0.1 %
(± 0.4 % for %r)

Absolute:

0.0 to 4000 mV x selected

1 mVrms x selected clamp scaling

± 5 % of reading ± 5 counts

clamp scaling

Watts

Relative:

0.0 to 100.0 %

0.1 %

± n x 2 %

Absolute:

depends on selected clamp

± 5 % of reading ± n x 2 %

and voltage scaling

of reading, ± 10 counts

DC voltage

Relative:

0.0 to 100.0 %

0.1 %

± 1 %

Absolute:

0.0 to 1000 V

0.1 V

± 5 % of reading ± 10 counts

THD

0.0 to 100.0 %

0.1 %

± 2.5 %

Hz

0 to 3500 Hz

1 Hz

± 1Hz

Phase angle

-360 º to +360 º

1 º

± n x 1.5 º

Power and Energy

Watt

1.0 W to 20.00 MW

1

0.1 W to 1 kW

1

± 1.5 % of reading ± 10 counts

3

VA

1.0 VA to 20.00 MVA

1

0.1 VA to 1 kVA

1

± 1.5 % of reading ± 10 counts

3

VAR

1.0 VAR to 20.00 MVAR

1

0.1 VAR to 1 kVAR

1

± 1.5 % of reading ± 10 counts

3

kWh

00.00 kWhr to 200.0 GWhr

1

0.01 Whr to 100 Whr

1

± 1.5 % of reading ± 10 counts

3

kVA

00.00 kVAhr to 200.0 GVAhr

1

0.01 VAhr to 100 VAhr

1

± 1.5 % of reading ± 10 counts

3

kVAR

00.00 kVARhr to 200.0 GVARhr

1

0.01 VARhr to 100 VARhr

1

± 1.5 % of reading ± 10 counts

3

Power Factor

0 to 1

0.01

± 0.03

3

Cos

ϕ / DPF

0 to 1

0.01

± 0.03

3

Flicker

Pst (1min), Pst, Plt, PF5

0.00 to 20.00

0.01

Within ± 5 % of tabulated values

instantenous Flicker

according IEC61000-4-15

Dc %, Dmax % and Time d(t)

0.0 to ± 100.0 % for Dc % and

0.1 % for Dc % and Dmax % and

± 1% for Dc % and Dmax % and

exceeds limits. As described

Dmax % and 0.000 to 9.999s

10 ms for Time

20 ms for Time

per IEC 61000-3-3

for Time

Unbalance

Volts

0.0 to 5.0 %

0.1 %

± 0.5 %

Current

0.0 to 20 %

0.1 %

± 1 %

Transient capture

Volts

± 6000 Vpk

1 V

± 15 % of cursor reading
± 2.5 % of Vrms

Minimum detect duration

5 µs

Sampling rate

200 kS/s

Inrush mode

Arms (AC+DC)

0.000 to 20.00 kArms

1

0.001 to 10 Arms

1

± 1 % of meas ± 5 counts

3

Inrush Duration

mm:ss:mmm between 7.5 s to

10 ms

± 20 ms (Fnominal = 50 Hz)

30 m selectable

Fluke 430 Series Three-Phase Power Quality Analyzers

Fluke Corporation 5