FieldServer FS-8700-105 User Manual

Page 18

Advertising
background image

FS-8700-105_National_Time_and_Signal_FACP Manual

Page 16 of 25


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]


Thus: A Comms Fail message puts the node offline and the node is put online when either a
valid message is received from the panel or the Comms Fail event is restored.

The driver reports the node status by updating the Data Array specified by the
NATSfacp_Status_DA parameter specified on the connection. If this parameter is not
specified then the node status cannot be reported. Ensure the Data Array is at least 33 items
long. The 1

st

element is used for the connection status. The remaining 32 elements are used

for node status. One element for each node and the offset corresponds to the Node_ID/Panel
number.

This is the only way that an upstream node can monitor if the node is online/offline. The
data obtained by this driver will always be made available to other drivers even if the node
associated with the driver is offline.

Advertising