FieldServer FS-8700-105 User Manual

Page 9

Advertising
background image

FS-8700-105_National_Time_and_Signal_FACP Manual

Page 7 of 25


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

1.06

Client Side Map Descriptors

4.1.1.

FieldServer Related Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name

Name of this Map
Descriptor

Up to 32 alphanumeric
characters

Data_Array_Name

Name of Data Array where
data is to be stored in the
FieldServer

One of the Data Array names
from “Data Array” section
above

Data_Array_Offset

Starting location in Data
Array

0 to maximum specified in
“Data Array” section above

Function

Function of Client Map
Descriptor

RDBC, WRBC, WRBX

4.1.2.

Driver Related Map Descriptor Parameters

Column

Title

Function

Legal Values

Node_Name Name of Node to fetch data from

One of the node
names specified in
“Client Node
Descriptor” above

Data_Type

You must specify one of the 4 choices.

If the ‘Any’ type is used then all messages will be
stored using the MD irrespective of the Data
Type.

Do not create two MD’s with all parameters the
same except that one has a specific Data Type and
the other has ‘Any’. The driver can only store data
in one MD.

Alarm
Trouble
Supervisory
Other
Any

Board

The Board Number. One set of Map Descriptors
required for each board.

1, 2, 3 etc...

Loop

The Loop number on the Board. One set of Map
Descriptors required for each loop.

1,2,3 etc

Port-Type

Use one of the 4 permitted values shown on the
right. You can abbreviate the port-types to use the
1

st

character.

Input; Output;
Fault; P(Other)

Address

The address and length are used to specify a range
of Port Numbers. Think of the Address as a
synonym for port.
Starting address of read block

1,2, 3 … etc