4 Inspection and Maintenance

4.1 Checking the temperature / pressure relief

valve and expansion relief valve

Actuate each valve manually by turning the valve cap and

check whether the water flows unhindered to the discharge

point via the tundish. Make sure both valves fit properly in idle

position.

4.2 Checking the charge pressure of the

expansion vessel

Block the water supply and open the nearest hot water tap to

reduce the pressure from the secondary water system.
Check the pressure of the expansion vessel at the

measurement point with a pressure gauge. If the pressure

is below 3.0 bar, increase it with an appropriate air pressure

pump.
NOTE: Only use original spare parts from Glow-worm for the

replacement of parts.

4.3 Maintenance Checklist

Reheating
Check the circulation pump annually.
Check the timer/time programme settings annually.
Reheating: does it deliver the desired deactivation

temperature? annually.
Solar cylinder
Bleed the heat exchanger if necessary annually.
Check the connections for leaks annually.
Check the temperature and pressure relief valve annually.
Checking the expansion relief valve annually.