SPECIFICATIONS - continued

GEH-7252

10

May 2003

g

GE Capacitor & Power Quality Products

Figure 5

5% and 8% Filter Power Factor vs Load

Leading PF For All Load

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1.10

0

20

40

60

80

100

120

Percent Filter Load

Pow

e

r

F

actor

Typical

Worst Case

Performance With Unbalanced Line Voltage (Typical)

Table 4

All Components at Nominal Values

and Worse Case Service Conditions

8% Filter 100% Load

5% Filter 100% Load

Nominal THID

5.12%

3.93%

1% Unbalance

5.28%

4.06%

2% Unbalance

5.82%

4.47%

3% Unbalance

6.62%

5.10%

8% Filter 30% Load

5% Filter 30% Load

Nominal THID

10.13%

7.06%

1% Unbalance

10.61%

7.45%

2% Unbalance

12.11%

8.21%

3% Unbalance

14.30%

10.46%