3. Check that moisture has not condensed on the filter components. If moisture is present, do not

proceed with startup until the moisture has been removed.

4. Disconnect the filter output from the drive.

5. Connect the filter to the utility.

WARNING

Use extreme caution to avoid contact with line voltage when checking for power. INJURY OR
DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.

6. Confirm that line voltage is present at the input terminals (A1, B1, C1) of the filter.

7. Confirm that line voltage is present at the output terminals (A2, B2, C2) of the filter.

8. Disconnect the filter from the utility.

9. Connect the filter output to the drive.

10. Refer to the drive user manual for the drive startup procedure. Observe all safety instructions in the

drive user manual.