3.0L GAS eNGINe SeRVICe ReCoMMeNdATIoNS

Maintenance Tasks

Level 1

Level 2

Level 3

Level 4

Recommended to

be done monthly/

10 hrs.

Task

Comp.

(Date-

Initials)

Required to be

done 3 months/

Break-in /30 hrs.

Task

Comp.

(Date-

Initials)

Required to

be done Semi-

Annually/50 hrs.

Task

Comp.

(Date-

Initials)

Required to be done

Annually/ 100 hrs.

Task

Comp.

(Date-

Initials)

14. Visually inspect the unit look-

ing for leaks, wear or damage,
loose connections or compo-
nents, and corrosion. Correct
as necessary.

•

•

•

•

15. Test the engine and transfer

switch safety devices. Correct
and/or adjust as necessary.

•

16. Initiate an automatic start and

transfer of the unit to site load
and exercise it for at least 1
hour looking for leaks, loose
connections or components,
and abnormal operating condi-
tions. Correct as necessary.

•

•

17. Start and exercise the unit at

full rated load (use a load bank
if the site load is not enough)
for at least 2 hours looking
for leaks, loose connections
or components, and abnormal
operating conditions. Correct as
necessary.

•

18. Change the engine oil.

•

19. Replace the engine oil filter(s).

•

•

20. Replace the engine air filter(s).

•

•

21. Replace the engine fuel filter(s)

on diesel engine driven units
and re-prime the fuel system.

•

•

22. Check the engine spark plugs

on gas engine driven units.
Clean and re-gap orreplace as
necessary.

•

•

23. Perform a 5 minute no-load

operational run of the unit
looking for any post service
problems.

•

•

24. Return the unit to standby

setup for operation when
required.

•

•

•

•