PNEG-524 Roof Exhaust Fan

7. ELECTRICAL INSTALLATION

Electrical Installation of the Fan

The electrical installation must be performed by a certified electrician in accordance with the
appropriate national and local electrical codes.

ANY VIOLATION OF ELECTRICAL WIRING CODES COULD JEOPARDIZE THE
AIRSTREAM WARRANTY.

Check the type of electrical service present, and make sure the fan to be wired is manufactured
to operate on the electrical service. The table

on page 7

entitled “Fan Model Specifications”

indicates the electrical service the fan is designed to utilize in the column labeled “Motor Phase
and Voltage”. The electrical service must match this specification.

The components to connect the electrical service to the fan need to be sized for the electrical
service present. The charts below illustrate the sizing information for

single phase 230 volt

,

three

phase 230 volt

and

460 volt

respectively. Use the appropriate information and size the following

electrical service components:

Electrical Service for Single Phase Operation 230 Volt

Electrical Service for Three Phase Operation 230 Volt

Electrical Service for Three Phase Operation 460 Volt

Transformer

The transformer size for the fan only is indicated in a KVA rating. Example: For a 24" fan the first
chart would be used. The KVA rating for the 2 horse power motor is 3.5 KVA. This KVA rating is
for the fan only. Your electrician will need to add the KVA requirements for the other electrical
components of the system in sizing the transformer.

Motor

H. P.

Range

Transformer Size

(Note B) (Minimum)

Copper Wire Size for Distance-Motor to

Disconnect in Feet up to:

Fusetron or

Equivalent Time

Delay Fuse AMP

0' - 50'

100'

200'

300'

0.5

1.0 KVA

14

14

12

10

10

2.0

3.5 KVA

12

10

6

5

30

Motor

H. P.

Range

Transformer Size

(Note B) (Minimum)

Copper Wire Size for Distance-Motor to

Disconnect in Feet up to:

Fusetron or

Equivalent Time

Delay Fuse AMP

0' - 50'

100'

200'

300'

0.5

1.0 KVA

14

14

14

14

10

2.0

3.5 KVA

14

12

10

8

15

Motor

H. P.

Range

Transformer Size

(Note B) (Minimum)

Copper Wire Size for Distance-Motor to

Disconnect in Feet up to:

Fusetron or

Equivalent Time

Delay Fuse AMP

0' - 50'

100'

200'

300'

0.5

1.0 KVA

14

14

14

14

10

2.0

3.5 KVA

14

14

12

12

10

WARNING