Greenheck Fan FD & DFD Series User Manual

Installation instruction supplement, Fd & dfd series, Fsd & ssfsd series

Advertising
background image

1

/

2

in. UL Classified

Gypsum Wallboard (see

UL Rated Wall Design

for Additional Details)

2

1

/

2

in. Min.

Stud or Runner

Damper

Sleeve

Angle Fastener

(see Note 2)

1

1

2

in. x 2

1

2

in.

16 ga. angle

Figure #2: 1 Hour Wall Rating

1

/

2

in. UL Classified

Gypsum Wallboard (see

UL Rated Wall Design

for Additional Details)

2

1

/

2

in. Min.

Stud or Runner

Damper

Sleeve

Angle Fastener

(see Note 2)

1

1

2

in. x 2

1

2

in. 16

ga. angle

Figure #3: 2 Hour Wall Rating

Figure #1: Opening Preparation Detail (double vertical

studs are not required for openings 36 in. x
36 in. [914mm x 914mm] or smaller)

12 in.

24 in. o.c.

Maximum

Floor Runner

2 in.

Ceiling Runner

2 Panhead

Screws

24 in. o.c.

Maximum

(metal studs)

24 in. o.c.

Maximum

(metal studs)

16 in. o.c.

Maximum

(wood studs)

16 in. o.c.

Maximum

(wood studs)

2 in.

Notes

1. Gypsum panels must be screwed 12 in. (305mm) on center

maximum to all stud and runner flanges surrounding
opening. (See Figure 1 for Opening Preparation Details).

2. Fire damper and sleeve assemblies 80 in. W x 50 in. H

(2032mm x 1270mm), 50 in. W x 80 in. H
(1270mm x 2032mm), or 40 in. W x 100 in. H
(1016mm x 2540mm) and smaller only require retaining
angles on one side of the partition. (See Figure 2 and
Figure 3). Retaining angles must be attached to the
sleeve and the partition. Larger damper assemblies require
retaining angles on both sides of the partition. Retaining
angles must be attached to the sleeve.

• Retaining angles must be a minimum of 16 gauge (1.5mm)

steel and have a minimum of 1

1

/

2

in. x 2

1

/

2

in. legs

(38mm x 63mm).

• Retaining angles must be attached to the sleeve using

one of the methods shown below:

• tack or spot welds
• #10 sheet metal screws and bolts

• Retaining angles must be attached to the partition using

drywall screws of a length such that the screw engages
the stud by a minimum of 1

3

/

4

in. (44mm)

• A minimum of two connections per side, top, and bottom,

12 in. (305mm) O.C. maximum for openings of
48 in. W x 36 in. H (1219mm x 914mm) and less, and
6 in. (152mm) O.C. for openings 80 in. W x 50 in. H
(2032mm x 1270mm), 50 in. W x 80 in. H,
(1270mm x 2032mm) and 40 in. W x 100 in. H
(1016mm x 2540mm)or less.

• Retaining angles must overlap the partition a minimum of

1 in. (25mm)

Copyright © 2008 Greenheck Fan Corporation

462102 Wood Stud Supplement

Rev. 4 March 2008

®

Part #462102

INSTALLATION INSTRUCTION SUPPLEMENT

Refer to:
‘Installation Instructions for FD, DFD, SSFD, & KFD Models’
(Part #452763)
or
‘Installation Instructions for FSD-XXX, DFD-XXX, & CFSD-XXX,
SSFSD-XXX Series Fire & Combination Fire Smoke Dampers’
(Part #461336)
or
‘Installation Instructions for FD & DFD 150X Series Curtain Fire
Dampers’ (Part #453946) for additional details.

Wood Stud Framing for Fire Dampers in Drywall
Partitions Utilizing One Retaining Angle

FD & DFD Series

1

1

/

2

Hour Curtain Fire Dampers

and

FSD & SSFSD Series

1

1

/

2

Hour Combination Fire Smoke Dampers

Vertical Mount

“UL CLASSIFIED

(see complete marking on product)”

“UL CLASSIFIED to Canadian safety standards

(see complete marking on product)”

Standards UL 555 & 555S

Classifications Filed at UL under Listing #R13317