PMCS Interface Toolkit

Troubleshooting Tips for the Annunciator Panel
Wizard

• Make sure that all DDE Items associated with the annunciator panel

have been created in the Event Logger.

• You must create associated InTouch DDE Integer Tags by hand in the

InTouch tagname database. The DDE Access name for the tags should
use “EVENTLOG” for the Application Name and “SYSTEM” for the
Topic Name. Make sure the “Request Initial Data” option is selected
for this DDE Access name.

• Check the WWLogger at runtime for possible DDE errors.
• Make sure your application script is mapping the proper DDE tags with

the proper indirect tags.

• Make sure the Event Logger is running before starting InTouch

Windowviewer.