Gentek photoelectric smoke alarm 9120 User Manual

Page 3

Advertising
background image

Figures 1, 2, 3, & 4 are reprinted with permission from NFPA 72, National Fire Alarm Code®,

Copyright ©2002, National Fire Protection Association, Quincy, MA 02169. This reprinted

material is not the complete and official position of the National Fire Protection Association on

the referenced subject which is represented only by the standard in its entirety. National Fire

Alarm Code® and NFPA 72® are registered trademarks of the National Fire Protection

Association, Inc., Quincy, MA 02169.

Figure 4: A SMOKE ALARM SHOULD BE LOCATED ON EACH

LEVEL IN ADDITION TO EACH BEDROOM.

Are More Smoke Alarms Desirable? The required number of

smoke alarms might not provide reliable early warning protection for

those areas separated by a door from the areas protected by the

required smoke alarms. For this reason, the use of additional smoke

alarms for those areas for increased protection is recommended. The

additional areas include the basement, bedrooms, dining room, fur-

nace room, utility room, and hallways not protected by the required

smoke alarms. The installation of smoke alarms in kitchens, attics (fin-

ished or unfinished), or garages is not normally recommended,

because these locations occasionally experience conditions that can

result in improper operation.

IMPORTANT CONSIDERATION

NFPA 72, 2010 Edition, Chapter 29, Section 29.8.1.4(5)(b)

states: “Smoke alarms installed in one- and two-family dwellings

shall not remain in service longer than 10 years from the date of

manufacture.” Smoke alarms should be replaced for the

following reasons:

Dust, dirt, and other environmental contaminants can affect your

smoke alarm over a prolonged period.

Fast changing industry consensus standards and codes on all

smoke alarms make it advisable to periodically upgrade your

devices to maximize life safety.

Assurance that your smoke alarm needs are kept abreast with the

constantly improving electronic technology.

Smoke alarms are recognized as one of the lowest cost ways to

protect dwelling inhabitants against the danger of fire(s). It makes

good common sense to periodically replace and update your

smoke alarm that contributes so much to life safety.

MOUNTING LOCATION

This smoke alarm can be mounted on a ceiling or wall with equal

efficiency in either location.

Ceiling location - smoke alarm should be mounted as close as

possible to the center of a hallway or room.

Wall location - locate the top of the smoke alarm not more than 12

inches from the ceiling.

Figure 2: A SMOKE ALARM SHOULD BE LOCATED BETWEEN THE

SLEEPING AREA AND THE REST OF THE DWELLING UNIT AS

WELL AS IN EACH BEDROOM.

In dwelling units with more than one bedroom area or with

bedrooms on more than one floor, more than one smoke alarm is

required, as shown in Figure 3.

Figure 1:

A SMOKE ALARM SHOULD BE LOCATED ON EVERY

LEVEL OF DWELLING UNIT, INCLUDING BASEMENT, WITHIN

EACH SLEEPING ROOM AND OUTSIDE SLEEPING AREAS.

Where to Locate the Required Smoke Alarms. The major threat

from fire in a dwelling unit occurs at night when everyone is asleep.

Persons in sleeping areas can be threatened by fires in the remainder

of the unit; therefore, smoke alarms are best located in each bedroom

and between the bedroom areas and the rest of the unit as shown in

Figure 2.

Figure 1

Figure 2

Figure 3

Figure 3: IN DWELLING UNITS WITH MORE THAN ONE

SLEEPING AREA, A SMOKE ALARM SHOULD BE PROVIDED TO

PROTECT EACH SLEEPING AREA IN ADDITION TO SMOKE

ALARMS REQUIRED IN BEDROOMS.

In addition to smoke alarms outside of the sleeping areas and in

each bedroom, NFPA 72 requires the installation of a smoke alarm on

each additional level of the dwelling unit, including the basement.

These installations are shown in Figure 4. The living area smoke

alarm should be installed in the living room or near the stairway to the

upper lever, or in both locations. The basement smoke alarm should

be installed in close proximity to the stairway leading to the floor

above. Where installed on an open-joisted ceiling, the smoke alarm

should be placed on the bottom of the joists. The smoke alarm should

be positioned relative to the stairway so as to intercept smoke coming

from a fire in the basement before the smoke enters the stairway.

Figure 4

550-0093

Page 9-3

29.5.1.1 Where required by applicable laws, codes or standards for a

specific type of occupancy, approved single and multiple-station smoke

alarms shall be installed as follows:

1) In all sleeping rooms and guest rooms

2) Outside of each separate dwelling unit sleeping area, within 6.4m

(21ft) of any door to a sleeping room, the distance measured along a

path of travel

3) On every level of a dwelling unit, including basements

4) On every level of a residential board and care occupancy (small

facility), including basements and excluding crawl spaces and

unfinished attics

5) In the living area(s) of a guest suite

6) In the living area(s) of a residential board and care occupancy

(small facility)

29.5.1.2 Where the area addressed in 29.5.1.1(2) is separated from

the adjacent living areas by a door, a smoke alarm shall be installed in

the area between the door and the sleeping room, and additional

alarms shall be installed on the living area side of the door as

specified by 29.5.1.1 and 29.5.1.3.

29.5.1.3 In addition to the requirements of 29.5.1.1(1) through

29.5.1.1(3), where the interior floor area for a given level of a dwelling

unit, excluding garage areas, is greater than 93m

2

(1000ft

2)

, smoke

alarms shall be installed per 29.5.1.3.1 and 29.5.1.3.2.

29.5.1.3.1 All points on the ceiling shall have a smoke alarm within a

distance of 9.1m (30ft) travel distance or shall have an equivalent of

one smoke alarm per 46.5m

2

(500ft

2

) is evaluated by dividing the total

interior square footage of floor area per level by 46.5m

2

(500ft

2

).

29.5.1.3.2 Where dwelling units include great rooms or vaulted/

cathedral ceilings extending over multiple floors, smoke alarms located

on the upper floor that are intended to protect the aforementioned area

shall be permitted to be considered as part of the lower floor(s)

protection scheme used to meet the requirements of 29.5.1.3.1.

The installation of additional alarms of smoke, heat or CO type

should result in a higher degree of protection. Adding alarms to rooms

that are normally closed off from the required alarms increases the

escape time because the fire does not need to build to the higher level

necessary to force smoke out of the closed room to the required

alarms. As a consequence, it is recommended that the householder

consider the installation of additional fire protection devices. However,

it should be understood that NFPA 72 does not require additional

smoke alarms over and above those called for in Figures 1, 2, 3 and 4

where required smoke alarms are shown.

Advertising