Battery installation, Mounting: plate & smoke alarm, Checkout & troubleshooting – Gentek photoelectric smoke alarm 9120 User Manual

Page 5: Smoke alarm wiring diagram

Advertising
background image

PLUG

SMOKE

ALARM

BLK

1

WHT

11

RED / YEL

10

VIO

7

VIO / BLK

6

BLU

3

ORN

9

YEL

4

BRN

2

BRN

5

GRAY

GRAY

8

12

HOT

NEUT

POWER

TANDEM

ALARM

CONTACTS

ACCESSORY

ALARM

CONTACTS

ISOLATED

THERMAL

WIRING TWO OR MORE SMOKE ALARMS

Tandem Installation

NOTICE: All smoke alarms in a tandem installation must be

controlled by the same fuse or circuit breaker. Otherwise tandem units

will not operate. Tandem will operate in the event of AC power failure if

battery is connected to the smoke alarm.

LIMITATIONS: A maximum of 12 smoke alarms (9120/9123 or

9220/9223) may be connected together. Do not exceed 125 feet

between each smoke alarm. Do not exceed 1125 feet between first

and last smoke alarm.

NOTICE: A maximum of six (6) smoke alarms of either model

9120/9123 or 9220/9223 with the relay options (F, TF, HF) may be

tandem interconnected.

Wire used for interconnection shall be in accordance with article

760 of the latest edition of National Electrical Code (NFPA 70) and

must not exceed a resistance of 10 ohms.

VAC

ELECTRICAL

BOX

SMOKE

ALARM

SMOKE

ALARM

QUICK DISCONNECT

TYPE PLUG

ELECTRICAL

BOX

HOT / BLACK

NEUTRAL / WHITE

TANDEM WIRE

RED / YEL

1. Run a minimum of 16 gauge, 3-conductor cable, plus ground (4

wires) to the first alarm junction box from a power supply and between

all smoke alarms that are to be connected together. Use ANSI/UL

Listed Class 1 wire. Power limited cable for multiple tandem

connections are available at many commercial electrical retail stores.

2. Make wire connections to the supplied plug-in connector as follows:

black to black, white to white, 3rd conductor to the red/yellow wire.

The red/yellow wire should be stripped to make the connection.

Connect ground wire between metal outlet boxes.

BATTERY INSTALLATION

1. Remove smoke alarm from mounting plate by turning counter-

clockwise.

2. Remove AC power connector and unsnap power leads from top of

the old battery. Snap new battery onto snaps and reinsert battery

through hole in back of smoke alarm. WARNING: Units with battery

back-up will not provide power or transmit an alarm to AC only units

in the event of an AC power failure. All battery back-up units in

tandem with good batteries will operate normally during an AC

power failure for a minimum of 24 hours.

3. Use only Duracell MN 1604 battery with the 9000 Series smoke

alarms. Available at many retail stores.

MOUNTING: PLATE & SMOKE ALARM

1. Lace the connector through the provided mounting plate and secure

the plate to the junction box.

2. Plug the wire connector into the smoke alarm base.

3. Place smoke alarm up to mounting plate, rotating it clockwise until

smoke alarm firmly snap locks into place. Keep smoke alarm

parallel to mounting plate so upper and lower tabs on plate seat

correctly into smoke alarm.

CHECKOUT & TROUBLESHOOTING

1. Turn test knob to NORMAL position and install battery and then

supply house power to smoke alarm. The red indicator light should

flash every 15-30 seconds, showing smoke alarm is Operating

properly.

2. If red light is not flashing or the green LED is not on:

a. Check that the battery is installed.

b. Check the connector plug and wire connections. NOTE: Be sure you

turn off power before checking wire connections.

c. If power supply and wiring check out, but red light does not flash or

green LED is still off, return the smoke alarm to manufacturer. See

TO RETURN A SMOKE ALARM.

d. When powering up smoke alarms in a tandem installation and all

smoke alarms sound immediately, inspect all smoke alarms for

those with an illuminated indicator light. These will be the trouble

units.

3. Testing with Test Knob:

a. Rotate test knob counter-clockwise to TEST 1 position and wait up

to 20 seconds for smoke alarm to sound. If smoke alarm does not

sound after 20 seconds, return smoke alarm for service.

b. After successfully testing smoke alarm, return test knob to NORMAL

(non-test) position and wait 20 seconds for alarm to stop sounding.

550-0093

Page 9-5

TO ADDITIONAL

SMOKE ALARMS

(MAX 12 ALARMS

PER SYSTEM)

LIMITATIONS

Maximum of 12

smoke alarms may be

connected together.

Do not exceed 125

feet between each

smoke alarm. Do not

exceed 1125 feet

between the first and

last smoke alarm.

Smoke Alarm Wiring Diagram

RATED LOAD RESISTIVE

1.0 AMP @ 24VDC MAX

0.6 AMP @ 125VAC MAX

0.56 AMP @ 220VAC MAX

CAUTION

RED/YELLOW wire to be

capped when not in use.

This wire is for tandem

connection only. Do not

connect to any other circuit.

START

FINISH

WORK CONNECTOR WIRES BACK

THROUGH HOLE IN ADAPTER PLATE

ROTATE ALARM TO UPRIGHT

POSITION

NOTES ON TANDEM INTERCONNECTING MODELS

DO NOT connect Gentex smoke alarms to other manufacturers'

smoke alarms.

No more than 12 Gentex models 9120T, H/9123T, H or 9220T, H/

9223T, H may be connected in tandem.

No more than 6 Gentex models 9120F, TF, HF/9123F, TF, HF or

9220F, TF, HF/9223F, TF, HF may be connected in tandem.

All units connected in tandem MUST get their power from the same

circuit, that is, all smoke alarms in tandem must be controlled by the

same fuse or circuit breaker.

After installation to verify proper working conditions all horns must

sound in this system.

NOTICE: If all interconnected alarms do not emit alarm signal during

commissioning test, refer to “WIRING TWO OR MORE SMOKE

ALARMS” section to insure alarm wiring is in accordance with tandem

wiring diagam.

CAUTION: Failure to observe any of the conditions set forth may

cause system malfunction and damage to the smoke alarm.

c. To test smoke alarm for high sensitivity, turn test knob clockwise to

TEST 2 position. Alarm should remain silent.

d. Make sure to return test knob back to its normal position.

e. If your smoke alarm sounds during this test it means the smoke

alarm's sensitivity has become too high and may cause false

alarms.