Appendix D Using the IC697CMM742 with PLC CPU Versions 4.12 - 5.50

D-3

D

6.

Connect a standard ASCII terminal or PC-based terminal emulator to the Station Manager
(RS-232) serial port on the Ethernet Interface. Use the NODE Station Manager command to
verify that the terminal or emulator is properly communicating with the Station Manager
software in the Ethernet Interface. A typical NODE command is shown below:

> node

IC697 PLC Factory LAN Ethernet Interface (Type 2)

Copyright (c) 1996. All rights reserved.

Version 1.10 (25A1) TCP/IP

Version 1.00 (12A1) Software Loader

IP Address = 0.0.0.0

MAC Address = 080019010688

*** PLC CPU version (5.00) supports restricted LAN

Interface operation:

*** SRTP server only (client operation is not permitted)

*** LAN Interface cannot be configured with PLC

Configurator

*** (Use CHSOSW Station Manager cmd to enter module

configuration)

*** PLC CPU version 6.00 or higher is required for full

operation

If the Ethernet Interface has not been previously configured, the NODE output will also
indicate that the Ethernet Interface is waiting for a valid IP address.

7.

Use the LOGIN Station Manager command to “log in” in order to access the Modify-level
commands needed later. The LOGIN command is shown below:

> login

After entering the LOGIN command, the Station Manager prompts for the Modify-level
password:

Password:

Enter your password (which is not echoed). The default password is: system (lower case).
If the password matches the current Modify-level password, a confirmation message is
displayed; the Station Manager prompt changes from “>” to “=”.

8.

Use the Modify-level MAINT Station Manager command to restart the Ethernet Interface
into the Maintenance state. The MAINT command is shown below:

= maint

Restarting module into Maintenance state

The Ethernet Interface is restarted into the Maintenance state. After approximately 20
seconds, another NODE output is automatically generated when the restart is complete. The
display will also indicate that the Ethernet Interface is in the Maintenance state; the Station
Manager prompt is “*”. Modify-level login is not required in the Maintenance state.