Goodmans COMMERCIAL HEATING & COOLING 3 TON - 6 TON PACKAGE GAS UNIT CPG SERIES User Manual

Page 27

Advertising
background image

27

APPENDIX A BLOWER PERFORMANCE TABLES

DIRECT DRIVE

CPG060 DOWN SHOT

SPEED

TAP

EXTERNAL STATIC

PRESSURE (ESP)

in w.c.

STANDARD

C FM

AMPS

WATTS

RPM

0. 10

1237

1.64

180

638

0. 20

1191

1.75

194

682

0. 30

1127

1.80

200

715

0. 40

1065

1.89

214

753

0. 50

994

1.97

220

797

0. 10

1437

2.13

248

687

0. 20

1384

2.24

254

726

0. 30

1312

2.29

262

759

0. 40

1245

2.42

280

803

0. 50

1185

2.54

294

847

0. 10

1988

4.49

558

885

0. 20

1942

4.58

574

907

0. 30

1882

4.69

582

935

0. 40

1847

4.80

600

962

0. 50

1784

4.87

612

990

0. 60

1762

4.97

626

1008

0. 70

1688

5.05

642

1039

0. 10

2106

5.14

650

924

0. 20

2050

5.26

670

951

0. 30

1993

5.32

678

969

0. 40

1960

5.47

696

1001

0. 50

1920

5.54

706

1021

0. 60

1880

5.61

726

1041

0. 70

1810

5.73

736

1072

0. 80

1760

5.81

750

1093

0. 90

1694

5.84

752

1122

0. 10

2199

5.87

762

968

0. 20

2146

5.96

772

989

0. 30

2121

6.06

788

1012

0. 40

2066

6.15

804

1039

0. 50

2010

6.21

814

1056

0. 60

1978

6.32

834

1084

0. 70

1919

6.28

830

1102

0. 80

1837

6.22

814

1122

0. 90

1738

6.04

786

1127

NOTES:

T5

CPG060 DIRECT DRIVE DOWN SHOT

Tab les represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM
correction for wet coil = 4 %. 5 T on models are shipped from the factory with speed tap set on T4.

T1

T2

T3

T4

Advertising