NSTALLATION REQUIREMENTS

(

CONT

.):

system. Refer to the VOLTAGE RATINGS & POWER SOURCE
CONFIGURATIONS” chart below. The TVSS model number can be found on the
front of the unit.

Verify that an NEC (National Electrical Code) compliant X0 bond has been made at
the upstream transformer that feeds the electrical supply panel. Per NEC 250.30, this
bond must be in place on all grounded electrical systems.

The TR5451 or TR5452 model TVSS must be installed on a dedicated branch circuit
breaker. The maximum allowable rating for the circuit breaker is 30A / 22kAIC.

Do not attempt to install the TVSS on the upstream (line) side of the Main Breaker or
Fuse.

The TVSS should only be installed indoors in NEMA 1 type locations. Do not install
the TVSS outside or in wet locations.

Single Phase

2 Wire + Ground

150V (L-N / L-G)

270V (L-N / L-G)

120V

240V

ACT451-120

ACT 451-240

Split Phase

3 Wire + Ground

150V (L-N / L-G)

270V (L-N / L-G)

120 / 240V

240 / 480V

ACT452-120

ACT452-240

SOURCE

CONFIGURATION

SYSTEM

TYPE

MAXIMUM

CONTINOUS RMS

OPERATING

VOLTAGE

NOMINAL

VOLTAGE

(50/60hZ)

MODEL

TYPE

L1

L2

N

VOLTAGE RATINGS & POWER SOURCE CONFIGURATIONS

L1

N

I

NSTALLATION

:

POWER MUST BE PROVEN DISCONNECTED BEFORE
STARTING INSTALLATION, INSPECTION OR MAINTENANCE!
FAILURE TO DO SO MAY CAUSE SERIOUS INJURY, DEATH
AND/OR PROPERTY DAMAGE
.

Before attempting installation, make sure that the pre-
installation requirements of this manual have been satisfied.
If the status of the pre-installation requirements are not
known, do not attempt to continue.

M

OUNTING

1. TR5451 and TR5452 TVSS units are designed to be
mounted directly to the electrical panel through a ½”
knockout. Mounting feet are also supplied for instances
where direct connection to the panel is not practical. Select
a location that will allow the closest proximity to the breaker
that the TVSS will be connected to.

2. Use the ½” threaded fitting and spacer to secure the
TVSS to the Electrical Panel that is to be protected.

903-640-0555
800-950-2281

NOTE: If lamp is out, replace unit

LISTED (48E6)

UL 1449, 2

ND

EDITION

FOR INDOOR USE ONLY

DUAL PHASE TVSS

120 VAC 50/60HZ

SUPPRESSION VOLTAGES

330 L-N
600 L-L

TVSS
PART# ACT452120210N
DATE CODE: WO#

Electrical
Panel

Spacer

Threaded
Fitting

ACT452-120

120V

150V (L-N / L-G)

TR5451-120



TR5451-240



TR5452-120