Local codes or plumbing authority requirements may vary from the instructions or diagrams provided in this
manual and take precedent over these instructions.

Tee fitting for vertical hot water
supply lines

Combination Potable and Space Heating Application

Tee fitting must be installed as shown.
This ensures that any air in the water
lines will be purged through the domestic
water faucets and showers.

DANGER:

When this system

requires water for space heating at
elevated temperatures (above 125°F
[52°C]), a mixing or tempering valve
must be installed in the hot water
supply line to the house in order to
reduce the scald hazard potential.

DANGER:

Any piping or components

used in the installation of this water
heater in a combination potable and
space heating application must be
suitable for use with drinking water.

DANGER:

If this water heater is

installed in an application intended to
supply domestic hot water needs and
hot water for space heating purposes,
do not connect the heater to an existing
heating unit or components of a heating
system that have previously been used
with a non drinking water system.
Toxic chemicals such as those used for
boiler treatment may be present and
will contaminate the drinking water
supply causing possible health risks.
Never introduce toxic chemicals, such
as those used for boiler treatment,
into this system.

!

!

!

Tee fitting for horizontal hot
water supply lines

Hot water
supply to
house

From HOT

outlet on

water heater

From HOT

outlet on

water heater

Hot water
supply to
heating
unit

Hot water
supply to
house

Hot water supply
to heating unit

R

E

L

I

E

F

V

A

L

V

E

CO

LD

HO

T

CO

LD

HO

T

Typical Piping Diagram for Combination Potable/Space Heating Installation

Spring loaded check valve in

heating unit hot water supply line

and cold water return line (not

supplied with water heater)

NOTICE: This check valve is

incorporated in some heating units.

Refer to the installation instructions

supplied with specific heating unit

to determine if it is required.

See diagrams above for proper

pipe application for vertical

or horizontal supply lines

Gas line to water heater

Cold water return
line from heating unit

Hot water
supply line into
heating unit

Heating unit

Isolation valve in cold
water return line from
heating unit (not
supplied with water
heater)

Water heater jacket

Temperature and pressure

relief valve discharge line

Drain valve
(not supplied
with water heater)

6” air gap

Isolation valve in hot water supply line

to heating unit

(not supplied with water heater)

Incoming cold water supply

Heat trap
6” Min.

Domestic hot water supply

Shut-off valve

Air vent

Temperature and pressure

relief valve

Combustion Air Inlet Openings

15

Supplemental instructions for gas water heaters
installed in potable/space heating applications.

Mixing or
tempering
valve (refer
to warning
above)

Thermal expansion tank
(if required-not supplied
with water heater)