Warn yes no, Auto on yes no, Additional control functions – GE Brocade FastIron power supply RPS12 User Manual

Page 4: Occupied, Time delay, Warn, Auto on

Advertising
background image

Catalog Number: RSP12

GE Lighting Controls, 41 Woodford Ave., Plainville, CT 06062

Made in U.S.A.

EMERGENCY SERVICE OR SUPPORT:
1-877-584-2685 (USA) or 1-800-661-6619 (Canada)

RSP12

0

WARN
YES
NO

AUTO ON
YES
NO

OCCUPIED

RED WHITE

WARN
YES
NO

O
N

1

RSP12

0

WARN
YES
NO

AUTO ON
YES
NO

OCCUPIED

RED WHITE

AUTO ON
YES
NO

2

RSP12

0

WARN
YES
NO

AUTO ON
YES
NO

OCCUPIED

RED WHITE

0 = NO TIME DELAY
1 = 15-MINUTE DELAY
2 = 30-MINUTE DELAY
3 = 45-MINUTE DELAY
…ETC. TO…
8 = 2-HOUR DELAY
9 = 1-MINUTE TEST

0

RSP12

0

WARN
YES
NO

AUTO ON
YES
NO

OCCUPIED

RED WHITE

MAINTAINED ISOLATED CONTACT

IN TIME CLOCK (BY OTHERS)

20/2 AWG 1000 FT. MAX.

ADDITIONAL CONTROL FUNCTIONS

Four optional control functions are available at the
bottom of the RSP12 board: Occupied, Time Delay, Warn
and Auto Off. Set these functions for all relays connected
to the RSP12 as a group, based on the needs at the site.

Occupied

The Occupied contact is available for connection with a
timeclock or building automation system. It indicates
when the building is operating under normal working
hours (CLOSED contact) or after hours (OPEN contact).
Properly connecting and scheduling the Occupied
contact determines when other functions will be enabled.

Time Delay

If the Time Delay function is set, when an occupant turns
on a switch after hours (Occupied contact OPEN), the
RSP12 will turn off the lights again after a predetermined
amount of time. Each occupant override will have its own
time delay.

Set the Time Delay dial as follows:

0

No time delay (no automatic off; lights must be
manually turned off)

1-8 15-minute to 2-hour delay, in 15-minute

increments

9

1-minute test

Warn

When the RSP12 turns relays OFF (at the end of normal
working hours, or at the end of a time delay), it will
optionally warn the occupants by blinking the lights five
minutes before they go off.

Set the WARN switch to YES or NO as follows:

YES

Gives a 5-minute warning before lights turn off

NO

Turns lights off without giving the warning

Auto On

When the Occupied contact closes at the start of normal
working hours, the RSP12 can optionally turn all the
relays ON automatically.

Set the AUTO ON switch to YES or NO as follows:

YES

Automatically turns all relays ON at start of
normal working hours

NO

Manual switch required to turn relays ON

OCCUPIED CONTACT

TIME DELAY

WARN SWITCH

AUTO ON SWITCH