Installation instructions, Site requirements, Flue and chimney requirements – Stovax 8542-P8542 User Manual

Page 11

Advertising
background image

11

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1.1

The chimney or flue system must comply with the rules in

force, and must be a minimum of 127mm in diameter. (5").

1.2

The minimum height of the flue or chimney must be 3 metres

(10ft). Any horizontal flue run from the rear outlet should not

exceed 100mm from the back of the appliance.

1.3

The chimney or flue must be free from any obstruction. Any

damper plates should be removed or secured in the fully open

position and no restrictor plates should be fitted.

1.4

The chimney should be swept prior to the installation of the

appliance, but where it can be seen that the chimney is clean

and unobstructed throughout its entire length, it need not be

swept.
NOTE: If it is intended to fit the stove into an existing brick-

built chimney without a closure plate*, a 5" (127mm) liner

must be used. Larger lined flues may work, but in some

instances could cause cold start flue problems resulting in

nuisance shutdown. Lined flues above 7" (175mm) are not

recommended.
Due to recent changes to European chimney standards, new

flues and chimneys are now described by their temperature,

pressure and resistance to corrosion, condensation and fire. To

assist in identifying the correct flue system, the minimum flue

specification is shown in the Technical Specification in this

manual. Existing chimneys are not covered by this system.

1.5

*Closure Plate Installation
Small and Medium stoves can be installed into a Standard,

fireplace opening with the optional closure plate and spigot

extension made for the appliance.
Note the stove and plate will require removing, when

carrying out the annual service.
The small Marlborough stove is also approved with a Closure

plate for installation into pre-cast letterbox flues conforming to

BS 1289:1986. with a minimum flue cross sectional area of

16500mm2 and a minimum dimension of 90mm.

2.1

The large stove has a rated output in excess of 7Kw and

requires a minimum of 11cm

2

permanent effective free air.

This is in addition to any window that opens, and although

it must communicate with the outside air whenver possible,

it can communicate with an adjacent room providing such

space has a similar opening to the outside. The small and

medium stoves have a rated output below 7Kw and do not

normally require any additional ventilation.

3.1

Before installation, ensure the local distribution conditions

(identification of the type of gas and pressure) and the

adjustment of the appliance are compatible.

3.2

Ensure that the gas supply is capable of delivering the

required amount of gas, and is in accordance with the rules

in force.

3.3

Soft copper tubing and soft soldered joints can be used but

must not be closer than 50mm to the base of the tray.

3.4

A means of isolating the gas supply to the appliance must

be provided, independent of any appliance control.

3.5

All supply gas pipes must be purged of any debris that may

have entered, prior to connection to the appliance.

4.1

This stove must stand on a non-combustible hearth that is at

least 12mm thick and projects 50mm minimum from the

base of the fire in all directions.

4.2

Do not install in a room that contains a bath or shower.

MINIMUM CLEARANCE
4.3

The stove is not suitable for installation against a

combustible wall. All combustible materials must be

removed from behind the fire.

4.4

Ensure you comply with all minimum clearance

measurements, whether or not to combustible materials.

The above dimensions provide adequate clearance at the

side and rear of the fire so that the controls can be reached.

3. INSTALLATION OF THE GAS SUPPLY

2. VENTILATION

4. APPLIANCE LOCATION

2

2A

1

Small Medium Large

A = 531mm 754mm 879mm
B = 442mm 527mm 568mm
C = 12mm

12mm

12mm

1. FLUE AND CHIMNEY REQUIREMENTS

AR0604

AR0531b

AR0531a

A

B

*

* Air-space to non-combustible

Advertising