TROUBLESHOOTING GUIDE

Problem Cause

Correction

The engine will not crank.

1. Fuse blown

1. Replace fuse.

2. Loose, corroded or defective

2. Tighten, clean or replace

battery

cables

as

necessary.

3. Defective engine Start/Stop

3. Replace Start/Stop switch.

switch

4. Defective starter contactor

4. Replace contactor.

5. Defective starter motor

5. Replace starter motor.

6. Low or defective battery

6. Charge or replace battery.

The engine cranks but

1. Out of fuel

1. Replenish fuel.

will not start.

2. Defective fuel solenoid

2. Replace fuel solenoid.

3. Open #14 wire from

3. Check connections and.

engine control board

insulation of #14 wires.

4. Flooded engine

4. Wait 5-10 minutes before trying.

5. Defective spark plug(s)

5. Clean, re-gap or replace plug(s).

6. Fuel line shut-off closed

6. Open fuel line shut-off.

The engine starts hard

1. Air cleaner

1. Check, clean or replace air cleaner.

and runs rough.

plugged or damaged

2. Defective spark plug(s)

2. Clean, re-gap or replace plug(s).

The engine starts, but shuts

1. Engine oil level low

1. Check oil and add oil as needed.

down when the Start/Stop

2. Defective low oil

2. Replace pressure switch.

switch is released.

pressure switch

3. Defective high temperature

3. Replace temperature switch.

switch

4. Defective engine control board

4. Replace control board.

5. Overheated engine

5. Check that the airflow

openings

are

adequate.

The Start/Stop switch is

1. Defective Start/Stop switch

1. Replace switch.

set to Stop, but the engine

2. Open/Disconnected #18 wire

2. Reconnect or close wire.

continues to run.

between Start/Stop switch

and engine control board

3. Open/Disconnected #0 wire

3. Reconnect or close wire.

between Start/Stop switch

and engine control board

4. Defective engine control board

4. Replace control board.

There is no AC output from

1. Main line circuit breaker open

1. Reset circuit breaker

the generator.

to ON (or closed).

2. Fault with vehicle circuit

2. Reset and replace if necessary.

breaker and/or fuses

3. Transfer switch set to NORMAL 3. Set switch to GENERATOR.

4. Start switch not held long

4. Stop, then restart the engine

enough to flash the field

(Hold Start switch for at least

2

seconds).

5. Generator internal failure

5. Contact an Authorized Service

Dealer.

Section 4 – Troubleshooting

Recreational Vehicle Generator