Goodman Mfg GPG13 User Manual

Page 32

Advertising
background image

32

GPG13(36)4A WIRING DIAGRAM

NOTE 4

NOTE 5

TR

WITH ECONOMIZER OPTION

BL

PU

RD

GR

WH

GR

RD

YL

BL

NO ECONOMIZER

WH

BL

R

C

Y

G

W

G

R

C

Y

W

GR

RD

YL

PU

2 STAGE COOLING

WH

C

G

R

Y2

Y1

W

NOTE 5

CHECK

EQUIP. STATUS

STATUS LIGHT

FAULT

INTERNAL CONTROL

NO POWER OR

NORMAL OPERATION

IGNIT ION FAILURE

SWITCH

OPEN

SWITCH

OPEN ROLLOUT

OPEN AUX. LIMIT

PRESSURE SWITCH

PRESSURE SWITCH CLOSED

WITHOUT INDUCER ON

COMPRESSOR

OPEN LIMIT SWITCH

OUTPUT DELAY

FALSE FLAME SENSED

5 BLINKS

4 BLINKS

2 BLINKS

6 BLINKS

3 BLINKS

1 BLINK

OR

OR

ON

OF F

CHECK

CHECK

PRESSURE SWITCH

PRESSURE SWITCH

3 MIN. COMP.

BAD SWITCH

STICKING GAS VALVE

MAIN LIMIT OPEN

ANTI-CYCLE TIMER

GAS FLOW

REPLACE CONTROL

CHECK INPUT POWER
CHECK FUSE ON CONTROL

GAS VALVE

BAD SWITCH

FLAME SENSOR

AUX. LIMIT OPEN

FLAME ROLLOUT

GAS PRESSURE

-

THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO

TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:

INSTALLER/SERVICEMAN

TO THERMOSTAT

1

3

IBR

R

W

G

9

10

7

ECON

IIC

3

6

8

F

5

4

H

C

Y1

Y2

12

11

C

Y

C

ALS

PS

D1

FS

LS

RS

GV

VMR

FS

L1

FC

EM

C

L1

T1

L1

VM

(HIGH)

(LOW)

FC

VMR

IGN

CM

IBR

CH

460/3/60

SUPPLY VOLTAGE

T2

T3

COMP

T1

T2

T3

NOTE 2

C

C

WH WHITE

YL YELLOW

1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF

INSUL ATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).

0140G00088

4. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT

SPEED REPLACE THE BLACK MOTOR LEAD AT IBR#3 WITH RED

3. 460V UNITS ARE SINGLE SPEED, TO CHANGE FROM HIGH TO LOW

THERMOSTAT FIELD WIRING

VENT M OTOR RELAY

VENT M OTOR

ROLLOUT SWITCH

TRANSFORMER

6. USE COOPER CONDUCTORS ONLY.

USE NEC CLASS 2 WIRE.

2. CRANKCASE HEATER NOT SUPPLIED ON AL L UNITS.

5. L1 AND L2 ON IIC CONTROL IS 24V INPUT.

2 SPEED MOTOR

BL - HIGH SPEED

RD/YL - LOW SPEED

TO BLOWER HOUSING IN RETURN AIR COMPARMENT.

LEAD FROM MOTOR.

3

6

PLF

4

2

1

5

VMR

RS

VM

TR

NOTES

460/3/60

LOW VOLTAGE

LINE VOLTAGE

LOW VOLTAGE

HIGH VOLTAGE

FIELD WIRING

GR GREEN

BR BROWN

BL BLUE

BK BLACK

WIRE CODE

PU PURPLE

OR ORANGE

OPTIONAL HIGH VOLTAGE

FACTORY WIRING

COMPRESSOR

COMPONENT LEGEND

PRESSURE SWITCH

LIMIT SWITCH

FLAME SENSOR

FAN CAPACITOR

EQUIPMENT GROUND

CRANKCASE HEATER

CONDENSER MOTOR

AUXILLARY LIMIT SWITCH

FEMALE PLUG/CONNECTOR

INTEGRATED IGNITION CONTROL

EVAPORATOR MOTOR

EM

L2

GAS VALVE

IGNITOR

IIC

IGN

GV

PS

PLF

LS

FUSE

F

GND

FS

FC

L2

L3

L2

L3

CONTACTOR

COMP

ALS

CH

C

CM

RD RED

PK PINK

IBR

INDOOR BLOWER RELAY

1

3

1

3

IIC

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.