Guardian Technologies Ademco VISTA-40 User Manual

Page 18

Advertising
background image

Р 18 Р

Compatible

Device Model #

Smoke Detectors

(System Sensor)

Photoelectric

2100

Photoelectric w/ 135

° heat

2100T

Photoelectric w/heat sensor, direct wire

2300T

Photoelectric, direct wire

2400

Photoelectric w/heat sensor, direct wire

2400TH

Photoelectric w/B401B base

2451

Photoelectric w/heat sensor & B401B base

2451TH

Ionization

1100

Ionization, direct wire

1400

Ionization w/B401B base

1451

Photoelectric duct detector w/DH400 base

2451

Ionization duct detect. w/DH400 base

1451DH

Zone 1 Advisories

If the EOLR is not at the end of the loop, the zone is not properly supervised. The system
may not respond to an open circuit within the zone.
The alarm current provided by this zone is sufficient to support operation of only one
detector in the alarmed state.

Hard-wired Zones 2Ð8

Applications

Can be used for EOLR supervised or closed circuit unsuper-
vised devices. EOLRs are required for UL installations. Can also
support 4-wire smoke detectors. Zone 8 can support latching
glass break detectors.

Zone Response Type

Any, except types 20Ð22 (these are used only for 5800 series
wireless transmitters).

Max. Zone Resistance ¥ Zones 2Ð7: 300 ohms, excluding EOLR

¥ Zone 1, 8: 100 ohms, excluding EOLR

Unsupervised Usage

¥ EOLR disabled in field *41 (enter 1).
¥ Only closed circuit devices can be used.

EOLR Supervised

¥ EOLR enabled in field *41 (enter 0).

¥ Supports both open circuit and closed circuit devices.
¥ Connect open circuit devices in parallel across the loop. The

2,000 ohm EOLR must be connected across the loop wires
at the last device.

¥ Connect closed circuit devices in series with the loop.

Glass Break Devices

¥ Supports up to 50 2-wire latching type glass break detectors.

on Zone 8

¥ Configure as EOLR zone.
¥ Second CODE + OFF sequence momentarily interrupts

power to reset the glass break detectors.

¥ See table that follows for compatible detectors.

Smoke Detectors

¥ Supports as many 4-wire smoke detectors as can be powered

on Zones 2Ð8

(see UL note on next page).

¥ Assign zone response type 09 (fire).
¥ The zones must be configured for EOLR supervision.
¥ A normally-closed, momentary switch must be installed in

series with the power to the detectors in order to allow reset of
the smoke detectors after an alarm.

¥ The detectors must be wired in parallel, with the EOLR at the

last detector for full supervision.

¥ To supervise power, a System Sensor No. A77-716 EOL

Relay Module is recommended.