110v operation – Grizzly G0466 User Manual
Page 9
 
Model G0466/G0469 Air Compressors
-
7
-
This machine must have a ground 
prong in the plug to help ensure that it 
is grounded. DO NOT remove ground 
prong from plug to fit into a two-
pronged outlet! If the plug will not 
fit the outlet, have the proper outlet 
installed by a qualified electrician.
SECTION 2: CIRCUIT
REQUIREMENTS
Figure 1. Typical type 5-15 plug and
receptacle.
Serious personal injury could occur 
if you connect the machine to the 
power source before you have com-
pleted the set up process. DO NOT 
connect the machine to the power 
source until instructed to do so.
110V Operation
Amperage Draw
The motors on the air compressors will 
draw the following amps:
G0466 Motor Draw ...................... 8 Amps
G0469 Motor Draw .....................14 Amps
Circuit Requirements
Only connect your machine to a cir-
cuit that meets the requirements below. 
Always check to see if the wires and 
circuit breaker in your circuit are capable 
of handling the amperage draw from your 
machine, as well as any other machines 
that could be operating on the same cir-
cuit. If you are unsure, consult a qualified 
electrician. 
Model G0466
Minimum Circuit Requirement ..... 15 Amp
Model G0469
Minimum Circuit Requirement ..... 20 Amp
Plug/Receptacle Type
Plug Type ..............NEMA 5-15 (
Figure 1)