How to connect, Warning, Remove junction box – GE 3800 User Manual

Page 15: Cut and strip the cordset, A. for subbase installation, B. for direct connect installation

Advertising
background image

REMOVE JUNCTION BOX

1 Remove the junction box cover by removing the

front two screws.

2 Remove the junction box by removing the top and

bottom rear screws. Note how the tabs on the lower
left side of the junction box serve to hold the side in
place. This will help when the box is being reinstalled.

1

Unit connector

Junction
box cover

Junction
box

15

Installation Instructions

265 VOLT ELECTRICAL SUPPLY

WARNING:

Connection of this 265 V AC product to a branch circuit
MUST

be done by direct connection in accordance with

the National Electrical Code. Plugging this unit into a
building mounted exposed receptacle is not permitted
by code.
These models must be installed using the appropriate
GE power supply kit for the branch circuit amperage
and the electrical resistance heater wattage desired.
Use the POWER CONNECTION CHART on page 17
to determine the correct kit required. One of the
following installation methods (A or B) must be used.

CUT AND STRIP THE CORDSET

1 Remove the cordset from the power supply kit.

Measure 6

″ down the cord from where it emerges

from the back of the nylon plastic connector
and cut the cord through at this point.

2 Carefully remove 3

″ of the cordset insulation

so as to expose the three insulated wires.

3 Strip 3/4

″ of the insulation away at the end

of each of the three wires (L1, Neutral and
Ground). Plug the connector fully into place
in the unit mating connector. Be sure the
locking tabs at the sides are engaged.

2

3/4

3

Connector

6

NOTE:

Order Kit RAK4002CW to enable a quick

disconnect inside the junction box.

A. FOR SUBBASE INSTALLATION

Electrical subbase kits are available to provide a flexible
enclosure for direct connection.

The instructions provided with the selected subbase kit must
be carefully followed. It is the responsibility of the installer
to ensure the connection of components is done in
accordance with these instructions and all electrical codes.

Branch Circuit and

Proper GE

Power

Unit Amperage Rating

Subbase Kit

Supply Kit

15

RAK204E15

RAK5172

20

RAK204E20

RAK5202

30

RAK204E30

RAK5302

B. FOR DIRECT CONNECT

INSTALLATION

If an electrical subbase is not used, direct connection to
branch circuit wiring inside the provided junction box must
be done in accordance with the following steps.

HOW TO CONNECT

1 Remove the room cabinet.
2 Connect to electrical power.
3 See the special instructions below for applicable

supply voltages.

4 Reinstall the room cabinet.