Sq 90-95, Direct drive – Greenheck Fan Greenheck Centrifugal Inline Fans SQ/BSQ User Manual

Page 18

Advertising
background image

18

Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound ratings shown are loudness values in fan sones at 1.5 m (5 feet) in a hemispherical free field calculated per AMCA International Standard 301. Values shown are

for installation type B: free inlet hemispherical sone levels.

1

(25)

Motor HP

Fan RPM

CFM / Static Pressure in Inches wg

Direct

0.000

0.125

0.200

0.250

0.300

0.375

0.400

0.500

0.600

0.625

90

VG-1/6

or 1/4

E-1/50

1050

CFM

500

370

271

188

BHP

0.02

0.02

0.02

0.02

Sones

4.0

3.9

4.0

4.1

G-1/25

1300

CFM

619

519

449

398

343

245

208

BHP

0.03

0.04

0.04

0.04

0.04

0.04

0.04

Sones

5.4

5.4

5.4

5.5

5.5

5.6

5.6

D-1/10

1550

CFM

738

655

603

565

522

457

435

334

BHP

0.05

0.06

0.06

0.06

0.07

0.07

0.07

0.07

Sones

7.6

7.5

7.5

7.4

7.4

7.4

7.4

7.4

1725

CFM

821

748

701

669

635

579

559

481

392

366

BHP

0.07

0.08

0.08

0.09

0.09

0.09

0.09

0.09

0.09

0.09

Sones

8.8

8.8

8.8

8.7

8.7

8.8

8.8

8.8

8.8

8.9

95

VG-1/6

or 1/4

E-1/30

1050

CFM

623

475

365

275

BHP

0.03

0.03

0.03

0.03

Sones

4.9

4.5

4.4

4.5

G-1/15

1300

CFM

771

660

580

523

461

352

311

BHP

0.05

0.06

0.06

0.06

0.06

0.06

0.06

Sones

7.6

6.7

6.5

6.4

6.4

6.4

6.4

D-1/8

1550

CFM

920

830

766

720

678

604

579

462

325

276

BHP

0.09

0.09

0.1

0.1

0.1

0.1

0.1

0.1

0.09

0.09

Sones

9.6

9.3

8.9

8.7

8.4

8.1

8.0

7.6

7.2

7.1

1725

CFM

1024

948

890

850

809

751

729

641

535

507

BHP

0.12

0.13

0.13

0.13

0.13

0.14

0.14

0.14

0.14

0.14

Sones

11.3

11.0

10.8

10.6

10.4

10.1

9.9

9.8

9.3

9.2

SQ 90-95

- Direct Drive

Damper size = 12 x 12

(305 x 305)

Unit weight** = 41

(19)

Housing thickness = 18 ga

Outlet velocity = 1.021 x cfm

Dimensions shown in inches (millimeters) and weight is

shown in pounds (kilograms).

**Weight shown is largest cataloged Open Drip Proof motor.

16

(406)

15

(381)

11

7

8

(302)

15

(381)

0

200

400

600

800

1000

1200

1400

1600

1800

0

20

40

60

80

100

120

140

160

180

200

220

0

200

400

600

800

1000

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

095-E

Static Pr

essur

e (in. wg)

Volume (cfm)

090-E

090-G

095-G

090-D

095-D

090-VG

095-VG

Volume (m

3

/hr)

Static Pr

essur

e (Pa)

RPM (Direct)
RPM (Vari Green)

Density 0.075 lb/ft
Density 1.2 kg/m

3

3

D

O

N

O

T

S

EL

EC

T

TO

T

H

E

LE

FT

O

F

TH

IS

S

Y

S

TE

M

C

U

R

VE