Filter options, Model selection procedure – Greenheck Fan Greenheck Centrifugal Inline Fans SQ/BSQ User Manual

Page 9

Advertising
background image

9

The filter box is designed to provide a compact and convenient clean
air solution. Factory-assembled as a single unit, this fan eliminates
the costly process of designing, fabricating and installing special
remote filter box assemblies. Both the fan and filter section feature
removable access panels on both sides to remove and replace
filters, making fan maintenance simple and fast.

Model

Fan

Size

Filter Box

Weight

Filter Size

Filter

Quantity

Filter Factor (F)

1 inch

(25)

2 inch

(51)

Aluminum

Paper Filters

(MERV 7)

Aluminum

Paper Filters

(MERV 8)

Model SQ

60 - 75

40

(18)

10 x 12

(254 x 305)

1

186

318.06

251.1

303.18

80 - 95

74

(34)

14 x 25

(356 x 635)

1

21.8

37.28

29.43

35.53

100

88

(40)

16 x 20

(406 x 508)

2

8.72

14.91

11.77

14.21

120

114

(52)

16 x 25

(406 x 635)

2

5.58

9.54

7.53

9.10

130

120

(54)

20 x 20

(508 x 508)

2

5.58

9.54

7.53

9.10

140

174

(79)

20 x 25

(508 x 635)

2

3.57

6.11

4.82

5.82

160

246

(112)

20 x 20

(508 x 508)

4

2.09

3.57

2.82

3.41

Model BSQ

70 - 80 - 90

117

(53)

14 x 25

(356 x 635)

1

21.8

37.28

29.43

35.53

100

120

(54)

16 x 20

(406 x 508)

2

8.72

14.91

11.77

14.21

120

144

(79)

16 x 25

(406 x 635)

2

5.58

9.54

7.53

9.10

130 - 130HP

140

(64)

20 x 20

(508 x 508)

2

5.58

9.54

7.53

9.10

140 - 140HP

181

(82)

20 x 25

(508 x 635)

2

3.57

6.11

4.82

5.82

160 - 160HP

294

(133)

20 x 20

(508 x 508)

4

2.09

3.57

2.82

3.41

180 - 180HP

344

(156)

20 x 25

(508 x 635)

4

1.34

2.29

1.81

2.18

200 - 200HP

441

(200)

12 x 25

(305 x 635)

3

0.77

1.32

1.04

1.26

16 x 25

(406 x 635)

3

240 - 240HP

573

(260)

20 x 25

(508 x 635)

4

0.41

0.70

0.55

0.67

16 x 25

(406 x 635)

4

300 - 300HP

759

(344)

20 x 25

(508 x 635)

8

0.33

0.56

0.45

0.54

360 - 360HP

957

(434)

16 x 25

(406 x 635)

10

0.15

0.26

0.20

0.25

20 x 25

(508 x 635)

5

420

1185

(538)

16 x 25

(406 x 635)

5

0.13

0.22

0.18

0.21

20 x 25

(508 x 635)

10

Note: 24-inch side clearance is recommended for accessing and removing filters.

All dimensions in inches (millimeters) and weight in pounds (kilograms).

Filter Options

Model Selection Procedure

1. Calculate system pressure drop and cfm requirements

(not including filters).

2. Make a preliminary model size selection.
3. Calculate a filter pressure drop (P) for the preliminary

model size selected in step 2 using the equation:

P = F

x

(

10,000

)

2

To determine the filter factor (F) refer to chart below.

4. Add the filter pressure drop (P) to the system pressure drop and make a revised model size selection.

cfm

Advertising