Generac Power Systems Digital Controller R-200A User Manual

Page 6

Advertising
background image

4

General Information

R-panel Technical Manual

Switch Position

Condition System

Low

Low

Low

High

Over

Over

Manual

Auto

Off

Ready

Fuel

Bat

Oil

Temp

Speed

Crank

Generator Switch is

OFF

@

X

OFF

OFF

OFF

OFF

O

in the OFF Mode

System Ready for

ON

@

X

OFF

OFF

OFF

OFF

O

Automatic Start

Generator Switch is

OFF

@

X

OFF

OFF

OFF

OFF

O

in the MANUAL Mode

Weekly Exerciser

X

@

Flashing Flashing Flashing

Flashing

Flashing

O

O

O

is not Set (Note A)

(---------------------------------------1 sec rate -------------------------------------)

Battery Voltage <12.2V

X

@

ON

O

O

O

for > 1 minute

(Non-Latching)

Battery Voltage <6V

OFF

@

ON

O

O

For > 0.05 seconds

Unit Shutdown due

OFF

@

X

ON

O

O

To Low Oil Pressure

Unit Shutdown due

OFF

@

X

ON

O

O

To High Cooant Temp

Unit Shutdown due

OFF

@

X

ON

O

O

To Engine Overspeed

Unit Failed to Start

OFF

@

X

ON

O

O

During it's Crank Cycle

Utility Voltage is

Flashing

@

X

O

O

< 60% of Nominal

1 sec rate

Unit Shutdown due

OFF

@

X

Flashing

O

O

To Low Coolant Level

Engine Speed Signal

OFF

@

X

Flashing

O

O

Fault/RPM Signal Loss

Control Board is

Flashing

@

X

O

O

O

In GTS Mode

5 sec ON, 1 sec OFF

DIP Switch #5 is

OFF

@

ON

ON

ON

ON

ON

O

O

O

not set correctly

@ = Low Fuel Pressure is a Yellow LED and will be ON when fuel pressure is less than 5 inches Water Column
X = indicates that the LED can be ON or OFF depending on the Operating Mode (i.e. Manual, OFF or Auto)
Note A: a RED LED fault indication has priority over the flashing LED's used to indicate exercise time not set