8 unpacking, 9 lifting the generator, 10 specifications – Generac Power Systems 005040-0 User Manual

Page 8

Advertising
background image

6

Generac

®

Power Systems, Inc.

Figure 1.6 - Low Coolant Level Sensor

1.7.4

OVERSPEED SHUTDOWN

Should AC frequency exceed about 72 Hz, circuit
board action will automatically shutdown the engine.

1.7.5

OVERCRANK SHUTDOWN

The engine control board uses a cyclic cranking
process when attempting to start the engine. The first
crank cycle is a 15-second crank followed by a seven-
second rest. This is followed by five more crank
cycles each with a seven second crank followed by a
seven-second rest.

If the engine fails to start after all six attempts, the start
attempt is stopped and the overcrank LED turns on.

1.7.6

LOW BATTERY

The engine control board continually monitors the
battery voltage and turns on the low battery LED if
the battery voltage falls below 12 VDC for one minute.
Low battery voltage is a non-latching alarm, which
will automatically clear if the battery voltage rises
above 12 VDC.

1.7.7

15A DC FUSE

This fuse is located inside the control panel. It pro-
tects the panel wiring and components from damag-
ing overload. The unit will not start or crank if the
fuse is blown. Replace the fuse with one of the same
size, type, and rating.

1.8

UNPACKING

1.8.1 UNPACKING PRECAUTIONS

Handle shipping cartons and crates with care. Use
care to avoid damage from dropping, bumping, colli-
sion, etc. Store and unpack cartons with the proper
side up, as noted on the shipping carton.

1.8.2 INSPECTION

Upon delivery, carefully inspect the generator for any
damage that may have occurred during shipment. If
loss or damage is noted at the time of delivery, have
the person(s) making delivery note all damage on the
freight bill or affix their signature under the consign-
or’s memo of loss or damage.

1.9

LIFTING THE GENERATOR

When lifting or hoisting equipment is used,
be careful not to touch overhead power lines.
The generators weight of more than 900
pounds requires proper tools, equipment, and
qualified personnel to be used in all phases of
handling and unpacking.

1.10 SPECIFICATIONS

1.10.1 ENGINE

Make ......................................................................................Ford
Displacement ............................................153 inches

3

(2.5 liters)

Cylinder Arrangement......................................................4, in-line
Valve Arrangement................................................Overhead Cam
Firing Order........................................................................1-3-4-2
Number of Main Bearings............................................................5
Compression Ratio..........................................................9.37 to 1
No. of Teeth on Flywheel ........................................................164
Ignition Timing (Waste Spark System)

at 1800 rpm ..................................................36 degrees BTDC

Spark Plug Gap ............................................................0.044 inch
Recommended Spark Plugs

Motorcraft ................................................................AWSF-52-C

Oil Pressure....................................................................30-50 psi
Crankcase Oil Capacity......................4.5 U.S. quarts (4.26 liters)
Recommended Engine Oil........................................SAE 15W-40
Type of Cooling System ..................Pressurized, closed recovery
Cooling Fan ..............................................................Pusher Type
Cooling System Capacity ......................2 U.S. gallons (7.6 liters)
Recommended Coolant ............Use a 50-50 mixture of ethylene

glycol base and deionized water.

Home standby control board assembly part
number 0E9704 must be used on 1800 rpm gen-
erators.

!

‹

!

‹

‹

‹

‹

‹

‹

Section 1 — General Information

Guardian Liquid-cooled 25 kW Generator

Advertising
This manual is related to the following products: