1.11 FUEL CONSUMPTION

25 kW Models

Using Natural Gas ........................................441 cu. ft. per hour
Using LP Gas ..............................175 cubic ft.(4.8 gal.) per hour

Fuel pressure for a natural gas set up should be five
inches to 14 inches of water column (0.18 to 0.5
psi) at all load ranges.

Fuel pressure for an LP vapor set up should be 11
inches to 14 inches of water column (0.4 to 0.5
psi) at all load ranges.

NOTE:

Fuel consumption is given at rated maximum con-
tinuous power output when using natural gas
rated at 1000 Btu per cubic foot; or LP gas rated
2520 Btu per cubic foot. Actual fuel consumption
obtained may vary depending on such variables as
applied load, ambient temperature, engine condi-
tions and other environmental factors.

1.12 RECONFIGURING THE FUEL

SYSTEM FOR LP VAPOR

NOTE:

All models are configured for natural gas from the
factory.

To reconfigure the fuel system from NG to LP vapor,
follow these steps:

1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet

port (Port 1) of the demand regulator (Figure
1.8).

3. Remove the brass hose fitting from the outlet port

(Port 1) of the demand regulator.

4. Remove pipe plug from Port 2.

5. Install brass hose fitting into Port 2.
6. Install pipe plug into Port 1.
7. Connect carburetor gas hose to brass fitting.
8. Tighten all clamps and plugs.
9. Make sure fuel supply is of the proper pressure

and type for configuration.

10. Move dip switch position 4 on the control board

to the off position (LP vapor, see Figure 3.2 and
Section 3.8).

11. Reverse the procedure to convert back to natural

gas.

Figure 1.8 — Reconfigure the Fuel System

NOTE:

Port 1 is for NG only and Port 2 is for LP vapor
only. No provision for dual fuel has been made.

Serious injury or damage may occur if not
configured properly. Please consult an author-
ized Generac Service Dealer with any ques-
tions.

!

DANGER

NG FUEL SYSTEM

LP FUEL SYSTEM

Port 1

Port 2

FUEL HOSE

BRASS HOSE
FITTING

OUT
PORT 2

PLUG

FUEL HOSE

BRASS HOSE
FITTING

FUEL INLET

PLUG

OUT

PORT 1

Section 1 — General Information

Guardian Liquid-cooled 25 kW Generator

Generac

®

Power Systems, Inc.

7

1.10.2 GENERATOR

‹

* Rated power of generator is subject to and limited by such factors as ambient temperature, altitude, engine condition,

and other factors. Engine power will decrease about 3.5% for each 1000 feet above sea level and will decrease an addi-
tional 1% for each 10°F above 60°F. Maximum output power of the generator is limited by maximum engine power.

Single-phase

Single-phase

Single-phase

Model

005040-0

005053-0

005054-0

Rated Max. Cont.

*25

20

15

AC Power Output (kW)
Rated voltage (volts)

120/240

120/240

No. of Rotor Poles

4

4

4

Driven Speed of Rotor

1800

1800

1800

Rotor Excitation System

Direct excited brush type

Direct excited brush type

Direct excited brush type

Type of Stator

4 Wire

4 Wire

4 Wire

Rotor Insulation

Class F

Class F

Class F

Stator Insulation

Class H

Class H

Class H