APPENDIX A BLOWER PERFORMANCE DATA

BELT DRIVE - HIGH STATIC

NOTES:

High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model.

Unit factory shipped with sheave set at 2.5 turns open.

Air flow tables represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

1.0

---

---

---

---

---

---

---

---

6690

3.69

6008

3.02

5321

2.43

1.2

---

---

---

---

---

---

6653

3.95

5922

3.22

5182

2.58

---

---

1.4

---

---

---

---

6634

2.80

5857

3.44

5056

2.74

---

---

---

---

1.6

---

---

6638

4.55

5808

2.43

4948

2.91

---

---

---

---

---

---

1.8

6683

4.93

5784

3.95

4855

2.05

---

---

---

---

---

---

---

---

2.0

5803

4.27

4788

3.32

---

---

---

---

---

---

---

---

---

---

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

1.0

---

---

---

---

---

---

9001

6.83

8394

6.01

7797

4.78

7227

4.28

1.2

---

---

---

---

8891

6.83

8262

6.15

7632

5.35

7012

4.20

---

---

1.4

---

---

8811

6.86

8148

6.15

7495

5.48

6841

4.71

---

---

---

---

1.6

---

---

8065

6.19

7377

5.48

---

---

---

---

---

---

---

---

1.8

7998

6.89

7290

5.52

---

---

---

---

---

---

---

---

---

---

2.0

7221

6.10

---

---

---

---

---

---

---

---

---

---

---

---

ESP, In H

2

O

TURNS OPEN

0

1

2

3

4

5

6

CPG240 HIGH STATIC BELT DRIVE

CPG180 HIGH STATIC BELT DRIVE

ESP, In H

2

O

TURNS OPEN

0

1

2

3

4

5

6