29

parallel UPS redundant and
for increased output

See figure 22.

■

isolate all UPSs

Proceed in the following order (see figure
23):

❏

shut down the inverters (press the

"inverter OFF" buttons 8 for three sec-
onds),

❏

close switch Q3BP and open switch

Q5N in the external bypass unit,

❏

open switches Q1, QF1 and Q5N on the

UPS units.

■

start-up

Following servicing, proceed in the follow-
ing order (see figure 24):

❏

close switches Q5N on the UPS units,

❏

close switch in the external bypass unit,

❏

open switch Q3BP in the parallel-con-

nection unit,

❏

close switches Q1 and QF1 on the UPS

units,

❏

start the inverters (press the "inverter

ON" buttons 7 ).

NOTE

We recommend that you
call on the after-sales
support department to
carry out these opera-
tions.
Note that for parallel
UPSs for increased out-
put, the entire installation
must be bypassed
because it is not possible
to isolate just one UPS
unit.

Maintenance

Fig. 24

Fig. 23

Fig. 22

2

3

4

5

1

0

1

0

1

0

1

0

Q5N

Q3BP

Q5N

Q1

Q4S

QF1

0

I

external bypass

7

5

6

1

Galaxy PW

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

2

3

4

5

1

0

1

0

1

0

1

0

Q5N

Q3BP

Q5N

Q1

Q4S

QF1

0

I

external bypass

7

5

6

1

Galaxy PW

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

2

1

Q3BP

Galaxy 1

Galaxy 2

2

1

Galaxy 3

2

1

Galaxy 4

2

Q5N

1

2

Q1

QF1

Q5N

Q4S

User’s Manual

Advertising