Timing chart:

You must turn the power off and on again to activate this parameter.

Home Position Return

Positioning with Digital Inputs

4 - 16

MITSUBISHI ELECTRIC

Fig. 4-5:

Home position return sequence in dogless Z-phase reference mode

PC04 “Home pos. return speed”

PC06 “Home offset”

PC05 “Creep speed”

Auto/Manual mode (MD0)

ON
OFF

Select point table no. (DI0)

Start command

Forward (ST1)

ON
OFF

Start command

Reverse (ST2)

ON
OFF

Servo motor speed setting

Z-phase of encoder

ON
OFF

Home return complete (ZP)

ON
OFF

No.

Code

Function

Description

PA05

*FTY

Feed length multi-
plication factor

Needed here to scale the home position value to the physical coor-
dinate system.

PC02

*ZTY

Home position re-
turn mode

Selects the home position return mode:
A: Dogless Z-phase reference mode

PC03

*ZDIR

Home position re-
turn direction

0: Incrementing counting of encoder pulses
1: Decrementing counting of encoder pulses

PC04

ZRF

Home position re-
turn speed

Sets home position return speed until first detection of the Z-phase
in [rpm].

PC05

CRF

Creep speed

Speed for precise movement to home position in [rpm].

PC06

ZST

Home position off-
set (shift)

Distance between the encoder zero point (Z-phase) and the physi-
cal home position in [µm].

PC07

*ZPS

Home position re-
turn position value

The home position return stops when the Z-phase position is
reached.You can enter a non-zero coordinate for this position [in
10

STM

µm] with this parameter.

Table 4-1: Parameter reference table