500kw containerized diesel generator set, Application data, Engine specifications – Multiquip MQ Power 500 kW Containerized Diesel Generator Set EGC500DD User Manual

Page 2: Engine electrical system, Derating

Advertising
background image

500kW Containerized

Diesel Generator Set

APPLICATION DATA

■ All ratings tested per MIL-STD-705 as applicable.
■ Generator protection for overload and short circuit.
■ Generator is designed and built within NEMA, IEEE and

ANSI standards for temperature rise.

■ PMG exciter for superior regulation and response.
■ Three phase sensing on regulator with EMI protection.
■ Skewed rotor for smooth voltage wave form.
■ Vacuum impregnated epoxy varnish - Fungus resistant per

MIL-I-24092.

■ Sustain short circuit current at 300% of rated current up to

10 seconds.

Alternator Features

Alternator Specifications

Make

Marathon Magna Max

Type

4-Pole, Rotating Field

Number of Leads

10 or 12

Generator Type

Rotating Field; PMG

Voltage Regulator

Solid State, Digital, Model DVR2000

Insulation

NEMA MG1-1.66

Material

Class H

Temperature Rise

Standby Rating: 125

o

C

Prime Rating: 105

o

C

Bearing: Number, Type

Single, Sealed

Coupling

Flexible Disk

Amortisseur Windings

Full

Voltage Regulation (no load to full load)

2% Maximum

One Step Load Acceptance % of rating per
NFPA-110

100

Peak Motor Starting HP

250

Generator Efficiency at Full Load

93%

Phase Sequence

ABC (L1, L2, L3)

L-L Harmonic Max Total

3.5%

L-L Harmonic Max Single

2.5%

Voltage Dip Upon Full Load Application (1 Step)

20% for 1.6 seconds

Voltage Rise Upon Full Load Rejection (1 Step)

14% for 0.6 of a second

Engine Specifications

Manufacturer/Model

Detroit Diesel 8V2000-G81

Engine Type

4-cycle, Turbocharged,

Air to Water Aftercooled

Cylinder Arrangement

V-8

Displacement

972 in

3

(16 liter)

Bore

5.12 in. (130 mm)

Stroke

5.91 in. (150 mm)

Compression Ratio

14.5:1

Piston Speed (60Hz)

29.5 ft./sec. (9.0 m/sec)

Bearing Main: Number

5

Bearing Main: Type

Replaceable, Precision

Cylinder Block

Cast iron

Cylinder Head Material

Cast iron

Crankshaft Material

Forged steel

Valves

Dual, Poppet Type

Brake Mean Effective Pressure (BMEP)

346 psi (2385 Kpa)

Rated RPM (60 Hz)

1800

Max. Power At Rated RPM (with fan)

765 hp (570.5 kW)

Governor: Type

Electronic

Frequency Regulation: No load to full load

+0.10 Hz

Frequency Regulation: Steady State

+0.05 Hz

Air Cleaner Type - All Models

Dry, Dual Element

Engine Electrical System

Battery Charging Alternator Ground Type

Negative

Volts

24 VDC

Ampere Rating

70A

Starter Motor Rated Voltage

24 VDC

Minimum Recommended Battery for

0 °C / Cold Cranking Performance

800 Ah

Derating

Derating Factors (60 Hz)

Altitude

Ambient

Temperature

The engine may be operated up to 2000 ft.
altitude and 40

o

C ambient temperature at the

St andby rating, wi thout derati ng. For
operation at higher altitudes and ambient
temperatures, the power should be derated
according to the following factors:

>2000 m =

4% per 500 m

>40

o

C =

1.5% per 5

o

C

Amperage

Voltage

Phase

Power
Factor

Continuous Amperes

Standby

Prime

120/208

3

0.8

1734

1561

277/480

3

0.8

752

677

The EGC500DD Sound Attenuated Generator is
configured for standard 60 Hz, 208V and 480V output.
Special voltage outputs are available (special
order)

.

EGC500DD Rev 2

Advertising