500kw containerized diesel generator set – Multiquip MQ Power 500 kW Containerized Diesel Generator Set EGC500DD User Manual

Page 3

Advertising
background image

500kW Containerized

Diesel Generator Set

Cooling System

Exhaust Manifold Type

Dry

Radiator Design

Standard horizontal discharge

Coolant Capacity - Engine

11.6 gal. (44 L)

Coolant Capacity - Engine and Radiator

42 gal. (159 L)

Water Pump Design/Type

Belt Driven, Centrifugal

Coolant Flow

79 gal/min (299 L)

Heat Rejection to Coolant

11535 BTU/min (202.7 kW)

Fan Horsepower

23 hp (17 kW)

Thermostat

188.6 °F (87 °C)

Fuel System

Recommended Fuel

ASTM-D975-No.1 or No. 2-D

Fuel Pump Maximum Lift

6.0 ft. (1.8 m)

Filter Micron Size - 98% Efficiency

2

Total Fuel Flow

186.1 gal./hr. (704.5 L/Hr.)

Fuel Consumption

Diesel Fuel @ % of Load

gal/hr

L/hr

25%

10.1

38.2

50%

18.1

68.5

75%

26.8

101.4

100%

37.7

142.7

Lubrication System

Type

Full Pressure System

Oil Filters

2 Spin-on, Full Flow

Oil Pan Capacity

12.2 gal. (46.0 L)

Oil Capacity with Filters

14.3 gal. (54.0 L)

Oil Pressure at Rated Speed

47 - 57 psi (324 - 393 kPa)

Exhaust System

Exhaust Temperature at Rated kW
(Dry Exhaust)

980

o

F (527

o

C)

Exhaust Flow at Rated kW

4080 cfm (115.5 m

3

/min)

Silencer Type

Critical

Maximum Allowable Backpressure

41.1 in/wc (10.2 kPa)

Exhaust Outlet Size at hook-up

5.0 in. (127 mm)

Inteligen Digital Genset Controller

■ Large graphic back-lit LCD display 128x64 pixel resolution
■ Automatic and manual starting and stopping
■ Phase sequence supervision
■ Automatic shutdown/alarm function
■ Input frequency 50-60 Hz
■ Parameters adjustable via PC or iG keyboard
■ Predefined and user definable configurations available.

One configuration includes set of inputs/outputs and parameters

■ Adjustable parameters for each configuration
■ 6 LED indicators
■ Push buttons for simple control
■ 4 programmable outputs (out of 20 functions selection)
■ 4 binary configuration inputs
■ Lamp test during start up
■ Real time clock
■ Sealed membrane panel to IP65
■ 180 x 113 mm front panel mounted case
■ Speed measurement from magnetic pickup
■ Oil pressure, Coolant temperature, Battery voltage and Fuel level

measurements

■ Running Hour Meter
■ All Generator metering, kVAr, kW, V1-V3, Hz, I1-I3, kWh, kVAh
■ Generator under/over voltage alarm/shutdown
■ Generator under/over frequency alarm/shutdown
■ Over Current alarm/shutdown
■ Warm up and cooling functions
■ Pre-lubrication function with timers
■ Adjustable crank attempts
■ Data logging
■ Remote communications (RS232/Modbus)

Digital Controller Features

EGC500DD Rev 2