MITSUBISHI ELECTRIC 700 Series User Manual

Page 87

Advertising
background image

82

Description of devices

(2) Present value update timing and accuracy in refresh system

1) The timer accuracy is +2 scan times independently of the used timer and scan

time.

2) The following shows the present value update timing and accuracy when the

10ms timer is used in a program where the scan time is 10ms or more.

Fig 3.17 Timer Timing Method

In Fig. 3.8, the time-out period of the 10ms timer T3 has the following errors.

*1 .......... 10ms timer error (+1 scan time)
*2 .......... Error produced by timer's input condition ON timing and OUT

T instruction's program position (+1 scan time)

The accuracy is +2 scan time (+0.05s in Fig. 3.8)

3) When the timer times out, its contact remains on until END even if the coil turns

off, and turns off at execution of the END instruction.

Ladder example

Timer timing method

T3 contact turns on 6s after X0 turns
on. (T3 is 10ms timer.)

OUT
T3

OUT
T3

OUT
T3

END

END

END

END

END

OUT
T3

END

Scan time 25ms

When external
input turns on
in hatched
range

*2

6000ms

*1

1

2

1

2

3

1

2

1

2

1

2

3

2

3

2

2

3

X0

T3 coil

T3 contact

10ms timer
timing

Timing set
at END

T3 present
value

OFF

OFF

ON

ON

ON

600 appears when monitored
on peripheral device.

25ms

25ms

25ms

25ms

OFF

1 scan
0

1 scan
0

0 3 3

3 2 5

597 2 599 599 3 602