9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-2

MITSUBISHI ELECTRIC 9700 SERIES UPS

D) External Battery Supply

Please refer to the following when installing batteries:

1. The customer shall make reference to the battery manufacturer's installation

manual for battery installation and maintenance instructions.

2. The maximum permitted fault current from the remote battery supply and the

DC voltage rating of the battery supply over-current protective device are
shown in Table 3.3.

TABLE 3.3 Maximum Permitted Fault Current

UPS CAPACITY

(kVA)

DC VOLTAGE

RATING (V)

MAXIMUM PERMITTED

FAULT CURRENT (A)

100 360 35000

150 360 25000

225 360 25000

300 360 25000

375 360 25000

3.3 Procedure for Cable Connections

A) Required metric tools – 19mm wrench, 19mm socket.
B) Confirm the capacity of the UPS being installed. Identify the input/output power

terminal blocks as shown in the appropriate Figure 3.1 through Figures 3.2-a~h.

C) Connect the internal control wire and power wire.

i) Control

wire

Inter-connect

a) AC input cabinet (300, 375kVA only)

(1) CB1-UVR to terminal 45, 46 in bypass cabinet section.
(2) CB1 Alarm to terminal 43, 44 in bypass cabinet section.
(3) CB1 Auxiliary connect to terminal 41, 42 in bypass cabinet section.
(4) Input transformer Over-temperature to terminal 52, 54 in bypass cabinet

section.

(5) Control power A, B, C phases (Terminal block) to A00, B00, C00 in

UPS converter section.

b) DC breaker cabinet or battery cabinet

(1) CB2-UVR to terminal 59, 60 (300, 375kVA) / 5, 6 (100, 150, 225kVA) in

bypass cabinet section.

(2) CB2 Alarm to terminal 57, 58 (300, 375kVA) / 1, 2 (100, 150, 225kVA)

in bypass cabinet section.