9700 SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-5

MITSUBISHI ELECTRIC 9700 SERIES UPS

Table 3.4 Recommended cable size and torque requirements

Input Side * 1, 2

Output Side * 1, 2

Bypass Side * 1, 2

DC Input Side * 1, 2

kVA

Capacity

Input

Voltage

Output

Voltage

Cable

Size

Torque

in. lbs.

Cable

Size

Torque

in. lbs.

Cable

Size

Torque

in. lbs.

Cable

Size

Torque

in. lbs.

100kVA

208V

208V

300 MCM

or larger

347 - 469

in. lbs.

300 MCM

or larger

347 - 469

in. lbs.

300 MCM

or larger

347 - 469

in. lbs.

250 MCM

or larger

347 - 469

in. lbs.

480V 480V 1/0

AWG

or larger

200 - 269

in. lbs.

1/0 AWG

or larger

200 - 269

in. lbs.

1/0 AWG

or larger

200 - 269

in. lbs.

250 MCM

or larger

200 - 269

in. lbs.

600V 600V 3

AWG

or larger

200 - 269

in. lbs.

3 AWG

or larger

200 - 269

in. lbs.

3 AWG

or larger

200 - 269

in. lbs.

250 M]

or larger

200 - 269

in. lbs.

150kVA

208V

208V

600 MCM

or larger

347 - 469

in. lbs.

600 MCM

or larger

347 - 469

in. lbs.

600 MCM

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

480V 480V 3/0

AWG

or larger

347 - 469

in. lbs.

3/0 AWG

or larger

347 - 469

in. lbs.

3/0 AWG

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

600V 600V 1/0

AWG

or larger

347 - 469

in. lbs.

1/0 AWG

or larger

347 - 469

in. lbs.

1/0 AWG

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

225kVA

208V

208V

3x250 MCM

or larger

347 - 469

in. lbs.

3x250 MCM

or larger

347 - 469

in. lbs.

3x250 MCM

or larger

347 - 469

in. lbs.

2x300 MCM

or larger

347 - 469

in. lbs.

480V 480V 300

MCM

or larger

347 - 469

in. lbs.

300 MCM

or larger

347 - 469

in. lbs.

300 MCM

or larger

347 - 469

in. lbs.

2x300 MCM

or larger

347 - 469

in. lbs.

600V 600V 4/0

AWG

or larger

347 - 469

in. lbs.

4/0 AWG

or larger

347 - 469

in. lbs.

4/0 AWG

or larger

347 - 469

in. lbs.

2x300 MCM

or larger

347 - 469

in. lbs.

300kVA

208V

480V

3x350 MCM

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

2x600 MCM

or larger

347 - 469

in. lbs.

480V 600

MCM

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

2x600 MCM

or larger

347 - 469

in. lbs.

600V 600V 400

MCM

or larger

347 - 469

in. lbs.

300 MCM

or larger

347 - 469

in. lbs.

300 MCM

or larger

347 - 469

in. lbs.

2x600 MCM

or larger

347 - 469

in. lbs.

375kVA

208V

480V

3x500 MCM

or larger

347 - 469

in. lbs.

700 MCM

or larger

347 - 469

in. lbs.

700 MCM

or larger

347 - 469

in. lbs.

3x400 MCM

or larger

347 - 469

in. lbs.

480V 2x250

MCM

or larger

347 - 469

in. lbs.

700 MCM

or larger

347 - 469

in. lbs.

700 MCM

or larger

347 - 469

in. lbs.

3x400 MCM

or larger

347 - 469

in. lbs.

600V 600V 600

MCM

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

500 MCM

or larger

347 - 469

in. lbs.

3x400 MCM

or larger

347 - 469

in. lbs.

*1 - Voltage drop across power cables not to exceed 2% of nominal source voltage

*2 - Allowable ampacities based on 90 degree C insulation at an ambient temperature of 30 degree C
Not more than 3 conductors in a raceway without derating.