Dca-220ssj/ssju — generator outputs – Multiquip MQ Power Whisperwatt 50 Hz Generator DCA-220SSJ User Manual

Page 44

Advertising
background image

PAGE 44 — DCA-220SSJ/SSJU— OPERATION AND PARTS MANUAL — REV. #1 (01/06/09)

DCA-220SSJ/SSJU — GENERATOR OUTPUTS

Generator Amperage

Tables 8 and 9 describe the generator’s current output capa-
bility for both 1Ø-phase and 3Ø phase applications.

Generator Output Voltages
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by apply-
ing jumpers (6) to the

voltage change-over board (Figure 15).

To obtain some of the voltages as listed in Table 6 (see
below) will require a fine adjustment using the

voltage regu-

lator (VR) control knob located on the control panel.

Voltage Change-Over Board
The

voltage change-over board (Figure 16) is located on

the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.

CAUTION - CHANGING VOLTAGES

NEVER attempt to place jumper plates on the

voltage

change-over board while the generator is in operation.
There exist the possibility of

electrocution, electrical

shock or burn, which can cause severe bodily harm
or even death
!

Figure 16. Voltage Change-Over Board

Table 7. Voltages Available

Three Phase

(Switchable)

200V

220V

400V

440V

Single Phase

(Switchable)

115V

127V

230V

254V

Table 8. Generator Ampere Ratings — 1Ø

kW

100V

200V

16

160

80

36

360

180

56

560

280

76

760

380

96

960

480

116

1160

580

136

1360

680

156

1560

780

176 (Max)

1760

880

Table 9. Generator Ampere Ratings — 3Ø

KVA

200V

400V

20

57

29

36

103

51

56

161

80

68

196

98

100

288

144

120

346

173

144

415

207

176

508

254

Advertising