Dca-220ssj/ssju — generator outputs/ gauge reading – Multiquip MQ Power Whisperwatt 50 Hz Generator DCA-220SSJ User Manual

Page 45

Advertising
background image

DCA-220SSJ/SSJU— OPERATION AND PARTS MANUAL — REV. #1 (01/06/09) — PAGE 45

1

Maximum Amps
Table 10 shows the

maximum amps the generator can pro-

vide. DO NOT exceed the maximum amps as listed.

How to Read the Output Terminal Gauge.
The AC ammeter and AC voltmeter change-over switches
on the control panel DO NOT effect the generator output.
They are provided to help observe how much power is being
supplied, produced at the UVWO terminals lugs.

When the voltage change-over board (Figure 16) is jumpered
for

3Ø,

240V operation place the

AC Voltmeter Change-

Over Switch (Figure 17) to the W-U position and the AC
Ammeter Change-Over Switch
(Figure 19) to the U or W
position. Use the AC voltmeter or AC ammeter (Figures 18
and 20) to read the output on the selected leg of the UVWO
terminals.

Figure 17. AC Voltmeter

Change-Over Switch

Figure 18. AC Voltmeter Gauge

(Volt reading on W-U Lug)

Figure 20. AC Ammeter

(Amp reading on U lug)

Figure 19. AC Ammeter

Change-Over Switch

The

ammeter gauge will only

show a reading when the
Output Terminal Lugs are
connected to a load and in use.

NOTE

DCA-220SSJ/SSJU — GENERATOR OUTPUTS/ GAUGE READING

Table 10. Generator Maximum Amps

Model

DCA-220SSJ/SSJU

Rated Voltage

Maximum Amps

Single Phase

100 Volt

466 amps (4 wire)

Single Phase

200 Volt

233 amps (4 wire)

Three Phase

200 Volt

508 amps

Three Phase

400 Volt

254 amps