52

Function (Parameter) list

P

a

ra

me

te

r L

ist

2.1 Function (Parameter) list

*1. The factory setting varies with the inverter capacity: 5% for FR-S540E-1.5K and 2.2K, 4%

for FR-S540E-3.7K.

CAUTION

indicates that the setting can be changed during operation if Pr. 77 "parameter

write disable selection" has been set to "0" (factory setting). (Note that the Pr. 53, Pr.
70 and Pr. 72 values can be changed only during PU operation.)

Parameter

Indica-

tion

Name

Setting

Range

Minimum

Setting

Increments

Factory

Setting

Refer

To:

Cus-

tomer

Setting

0

Torque boost

0 to 15%

0.1%

6%/5%/

4%/

(*1)

67

1

Maximum frequency

0 to 120Hz

0.1Hz

60Hz

68

2

Minimum frequency

0 to 120Hz

0.1Hz

0Hz

68

3

Base frequency

0 to 120Hz

0.1Hz

60Hz

69

4

Multi-speed setting
(high speed)

0 to 120Hz

0.1Hz

60Hz

70

5

Multi-speed setting
(middle speed)

0 to 120Hz

0.1Hz

30Hz

70

6

Multi-speed setting
(low speed)

0 to 120Hz

0.1Hz

10Hz

70

7

Acceleration time

0 to 999s

0.1s

5s

71

8

Deceleration time

0 to 999s

0.1s

5s

71

9

Electronic thermal O/L
relay

0 to 50A

0.1A

Rated

output

current

73

30

Extended function
display selection

0, 1

1

0

84

79

Operation mode
selection

0 to 4, 7, 8

1

0

113