Installation and User Manual
3.3
Information Technology IT Network and Industrial Operating Modes
Table 3-5: System Operation in IT Netowrk and Industrial Modes.
Symptoms
IT Network mode
Industrial mode
Overload, and Bypass
Load is transferred to Bypass AC source.
Same as IT Network mode, but AC
source in tolerance.
UPS returns to normal mode if overload
to the UPS does not return to
is removed.
normal mode if overload
is removed.
Overload, and Bypass
The UPS shuts down and load is not
Load is transferred to Bypass
AC source not in tolerance.
transferred to Bypass AC source.
AC source with 10 milli-
seconds output break.
The UPS does not return to
normal mode if overload
is removed.
Output short circuit and Bypass
The load remains powered by the UPS.
Load is transferred to Bypass
AC source in tolerance.
The UPS shuts down after 3 minutes
AC source. The UPS does not
if the short circuit remains.
return to normal mode if the
short circuit is removed.
Output short circuit and Bypass The load remains powered by the UPS.
The load is transferred to
AC source not in tolerance.
The UPS shuts down after 3 minutes
Bypass AC source with
if the short circuit remains.
10 milliseconds output break.
The UPS does not return to
normal mode if the short circuit
is removed.