MGE UPS Systems EX-7 User Manual

Page 66

Advertising
background image

Table 5-7: Efficiency on ECO mode (all kinds of load) and batteries fully charged.

5.6

Heat Rejection

Table 5-8: Full load heat rejection in BTU’s/hr.

System

Operation Mode

On-line

On Battery

5kVA

1350

1861

7kVA

1654

2280

11kVA

3033

3723

5.7

Environmental Characteristics

◗

The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to

+25°C range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.

◗

The storage temperature: -20 to 40°C. Humidity: 5-95%, non condensing.

◗

Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera-

tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers

no longer guarantee operation due to the risk of thermal runaway.

◗

Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.

kVA / kW

25%

50%

75%

100%

Output load percentage

5kVA /
4kWatts

96

95

97

96

96

96

97

96

Output: 220 / 230 / 240 Volts

Output: 200 / 208 / 250 Volts

7kVA /
4.9kWatts

96
95

97
96

96
96

97
96

Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts

11kVA /
8kWatts

96
95

97
96

96
96

97
96

Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts

EX 5/7/11RT Systems

Appendix

5 — 4

86-86000-00 B00