Table 5-7: Efficiency on ECO mode (all kinds of load) and batteries fully charged.

5.6

Heat Rejection

Table 5-8: Full load heat rejection in BTU’s/hr.

System

Operation Mode

On-line

On Battery

5kVA

1350

1861

7kVA

1654

2280

11kVA

3033

3723

5.7

Environmental Characteristics

The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to

+25°C range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.

The storage temperature: -20 to 40°C. Humidity: 5-95%, non condensing.

Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera-

tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers

no longer guarantee operation due to the risk of thermal runaway.

Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.

kVA / kW

25%

50%

75%

100%

Output load percentage

5kVA /
4kWatts

96

95

97

96

96

96

97

96

Output: 220 / 230 / 240 Volts

Output: 200 / 208 / 250 Volts

7kVA /
4.9kWatts

96
95

97
96

96
96

97
96

Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts

11kVA /
8kWatts

96
95

97
96

96
96

97
96

Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts

EX 5/7/11RT Systems

Appendix

5 — 4

86-86000-00 B00