11. TROUBLESHOOTING


11.2.2 Remedies for alarms

CAUTION

When any alarm has occurred, eliminate its cause, ensure safety, then reset the

alarm, and restart operation. Otherwise, injury may occur.

If an absolute position erase alarm (AL.25) occurred, always make home position

setting again. Otherwise, misoperation may occur.

POINT

When any of the following alarms has occurred, always remove its cause

and allow about 30 minutes for cooling before resuming operation. If
operation is resumed by switching control circuit power off, then on to reset
the alarm, the servo amplifier and servo motor may become faulty.

Regenerative error (AL.30)
Overload 1 (AL.50)
Overload 2 (AL.51)

The alarm can be deactivated by switching power off, then on press the

"SET" button on the current alarm screen or by turning on the reset (RES).
For details, refer to section 11.2.1.

When an alarm occurs, the trouble (ALM) switches off and the dynamic is operated to stop the servo

motor. At this time, the display indicates the alarm No.

The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. The

optional MR Configurator (servo configuration software) may be used to refer to the cause.

Display Name

Definition

Cause

Action

1. Power supply voltage is low.
2. There was an instantaneous

control power failure of 60ms or
longer.

3. Shortage of power supply capacity

caused the power supply voltage to
drop at start, etc.

4. The bus voltage dropped to the

folllowing value or less.
MR-J2S- CP: 200VDC
MR-J2S- CP1: 158VDC

Review the power supply.

AL.10 Undervoltage Power supply

voltage dropped.

MR-J2S- CP:

160VAC or less

MR-J2S- CP1:

83VAC or less

5. Faulty parts in the servo amplifier

Checking method

Alarm (AL.10) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.

Change the servo amplifier.

AL.12 Memory error 1 RAM, memory fault
AL.13 Clock

error Printed

board

fault

Faulty parts in the servo amplifier

Checking method

Alarm (any of AL.12 and 13)

occurs if power is switched on

after disconnection of all cables

but the control circuit power

supply cables.

Change the servo amplifier.

1. Faulty parts in the servo amplifier

Checking method

Alarm (AL.15)

occurs if power is switched on

after disconnection of all cables

but the control circuit power

supply cables.

AL.15 Memory error 2 EEP-ROM fault

2. The number of write times to EEP-

ROM exceeded 100,000.

Change the servo amplifier.

1. Encode connector (CN2)

disconnected.

Connect correctly.

2. Encoder fault

Change the servo motor.

AL.16 Encoder

error

1

Communication
error occurred
between encoder
and servo amplifier. 3. Encoder cable faulty

(wire breakage or short)

Repair or change the cable.