Appendix, 1 technical data, Output currents and voltage – MGE UPS Systems 30A User Manual

Page 27: Permissible-overload curve, Thermal characteristics

Advertising
background image

34020113EN/AA

- Page 27

6. Appendix

6.1 Technical data

Output currents and voltage

Rated output current:

Input and output voltage:

◗

Rated operating voltage:

◗

Maximum voltage:

◗

Minimum voltage:

◗

Rated frequency:

30 A

380 V / 400 V / 415 V

498 V (415 V +20%)

247 V (380 V -35%)

50 or 60 Hz (45 Hz minimum, 66 Hz maximum)

60 A 100 A160 A250 A400 A600 A

Permissible-overload curve

◗

During an overload, transfer between sources is disabled.

◗

Overloads higher than 1.5 In are stored in memory. The alarm must be reset to return to normal operation.

Thermal characteristics

(1) These characteristics are calculated for a voltage of 400 V and a power factor of 0.8.

Heat losses

(1)

:

◗

at rated power:

◗

at 50% rated power:

Required ventilation:

195 W
150 W

350 m

3

/h

295 W
195 W

350 m

3

/h

430 W
260 W

350 m

3

/h

615 W
350 W

1600 m

3

/h

920 W
495 W

1600 m

3

/h

1420 W

735 W

2300 m

3

/h

2150 W
1070 W

2300 m

3

/h

Noise level

Recommended protection devices upstream of Upsilon STS

Cable sizes

Noise in dB (ISO 3746):

Cross-sectional area in mm

2

:

50

50

50

120

120

240

240

Type of circuit breaker:

◗

TNS system:

◗

TNC system:

Trip unit:

Thermal setting:

Magnetic setting:

C60L 32A

curve C

1.05 In

10xIn

NS100H 4P 4D

NS100H 3P

STR22SE

≤

1.05 In

≤

10xIn

NS160H

4P 4D

NS160H

3P

STR22SE

≤

1.05 In

≤

10xIn

NS400H

4P 4D

NS400H

3P

STR23SE

≤

1,05 In

≤

10xIn

NS250H

4P 4D

NS250H

3P

STR22SE

≤

1.05 In

≤

10xIn

NS630H

4P 4D

NS630H

3P

STR23SE

≤

1.05 In

≤

10xIn

55

55

55

59

59

59

59

In

2 In

4 In

8 In

32 In

16 In

t(s)

0.01 s

0.1 s

1 s

10 s

100 s

1000 s