Dca-600ssk — output terminal panel overview – Multiquip DCA-600SSK User Manual

Page 33

Advertising
background image

DCA-600SSK — OPERATION AND PARTS MANUAL (STD)— REV. #7 (04/30/10) — PAGE 33

120 VAC GFCI Receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R)
recepacles provided on the output terminal panel. These
receptacles can be accessed in any

voltage change-over

board position. Each receptacle is protected by a 20 amp
circuit breaker. These breakers are located directly above
the GFCI receptacles. Remember the load output (current)
of both GFCI receptacles is dependent on the load
requirements of the UVWO terminals.

Pressing the

reset button resets the GFCI receptacle after

being tripped. Pressing the "

Test Button" (See Figure 9) in

the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.

Figure 9. G.F.C.I. Receptacle

Each auxiliary receptacle is protected by a 50 amp circuit
breaker. These breakers are located directly above the GFCI
receptacles. Remember the load output (current) on all three
receptacles is dependent on the load requirements of the
UVWO terminals.

Turn the

voltage regulator control knob (Figure 11) on the

control panel to obtain the desired voltage. Turning the knob
clockwise will

increase the voltage, turning the knob counter-

clockwise will

decrease the voltage.

Figure 10. 240/139 VAC Twist-Lock

Auxiliary Receptacles

DCA-600SSK — OUTPUT TERMINAL PANEL OVERVIEW

Twist Lock Dual Voltage 240/139 VAC Receptacles
There are three 240/139 VAC, 50 amp auxiliary twist-lock
(CS-6369) receptacles (Figure 10) provided on the output
terminal panel. These receptacles can be accessed in any
voltage change-over board
position.

Access to UVWO Terminals
The UVWO terminal lugs are protected by a terminal cover
(Figure 12). Un-lock the locking latch, and lift the terminal
cover to gain access to the UVWO terminals.

After the load wires have been securely attached to the
UVWO terminals, place the terminal cover in the down
position and secure the locking latch.

Figure 11. Voltage Regulator Control Knob

Figure 12. Terminal Cover (UVWO Terminals)

Advertising