DCA-600SSK — OPERATION AND PARTS MANUAL (STD)— REV. #7 (04/30/10) — PAGE 39

2. Connect the load wires to the UVWO terminals as shown

in Figure 27.

DCA-600SSK — OUTPUT TERMINAL PANEL CONNECTIONS

3Ø-480V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 480V operation

as shown in Figure 26. This configuration uses 6 jumper
plates in 3 different positions. Remember there are 2
jumper plates at every position. Every jumper plate

must

be used.

Figure 26. Voltage Change-Over Board

480V

Configuration

Figure 27. UVWO Terminal Lugs

3Ø-480V Connections

1Ø-480V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered

for 480V operation as shown in Figure 26.

2. Connect the load wires to the UVWO terminals as shown

in Figure 28.

1Ø-277V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered

for 480V operation as shown in Figure 26.

2. Connect the load wires to the UVWO terminals as shown

in Figure 29.

Figure 29. UVWO Terminal Lugs

1Ø-277V Connections

ALWAYS make sure that the
connections to the UVWO
terminals are

secure

and tight.

The possibility of arcing exists,
that could cause a fire.

NOTE

NEVER attempt to connect a load to the UVWO output
terminals while the generator is operating. The possibility
exists of serious injury, electrical shock, electrocution even
death.

Figure 28. UVWO Terminal Lugs

1Ø-480V Connections

DANGER - UVWO OUTPUT TERMINALS