Master Bilt Refrigeration Solutions TAF-48 ERC2 User Manual

Page 9

Advertising
background image

9

To initiate a Manual Defrost, press and hold the MAN DEF key for 3 seconds.

There are two levels of programming in the ERC 2. The first level of security will enable the user to
set two parameters: Time-of-day (

CLoC

) and Set point temperature (

SEt

). The other level allows

access to the other parameters.


Three buttons are used for the programming: SET, UP and DOWN

Fig. 4 – Display Lay-out


To change time-of-day and set point temperature (First Level) follows these steps:

Step 1

Press and hold set for 5 seconds. The display will show

CLoC

Step 2

Press SET again to change the time-of-day

Step 3

or

Press UP or DOWN until the correct time-of-day is displayed

Step 4

Press SET to accept the new time

Step 5

Press DOWN to go to the next parameter – Set point
Temperature - (cut out)

Step 6

Press SET to change the set point temperature

Step 7

or

Press UP or DOWN to go to the desired set point. The range is
– 40 to 60

°

F or –40 to 16

°

C

Step 8

Press SET to accept the change

Step 9

Press DOWN to exit the first level of programming


Note 1: During programming, if no button is pushed during 30 seconds, the control will go
back to the normal operating mode. This is valid for both programming levels.

Note 2: When changing the time, press and hold the MAN DEF button for 3 seconds to
change the AM/PM mode.

Note 3: Master-Bilt’s Set point Temperature (

Set)

is set at a recommended –10

°

F at the

factory for low temperature(LT) and +35

o

F for medium temperature(MT) application.

Note 4: If demand defrost (

ddEF

) is used, the minimum number of defrost is 1 per 24 hours.