Maintenance, 1 hot swapping the power sub-module, 2 hot swapping the battery sub-module – MGE UPS Systems 5000 RT User Manual

Page 32

Advertising
background image

34008030EN/AA

- Page 32

7. Maintenance

7.1 Hot swapping the power sub-module

Disconnecting the power sub-module :

Reconnecting the power sub-module :

7.2 Hot swapping the battery sub-module

Disconnecting the battery sub-module :

This operation must be carried out by qualified electrical personnel only.

This operation can be performed without interrupting the equipments.

1 - Remove the 6 fixing screws to free the
main front panel bezel.
2 - Place the front panel above the UPS.
3 - Remove the 4 fixing screws on the left side
to free the power sub-module.
4 - Withdraw the power sub-module.

◗

Carry out the above instructions in reverse order.

◗

Replace the faulty power sub-module by another one with same power rating (Pulsar MX 4000 or Pulsar MX 5000).

◗

Caution: a battery can cause electrocution and high short circuit currents.

◗

Servicing of batteries should be performed or supervised by personel knowledgeable of batteries and the required

precautions. Keep unauthorized personel away from batteries.

◗

Remove watches, rings, bracelets and all other metal objects from the hands and arms,

◗

Use tools with an insulated handle.

◗

When replacing batteries, replace with the same number of the BB/HR5.5-12 batteries.

This operation can be performed without interrupting the equipments.

1 - Remove the 6 fixing screws to free the
main front panel bezel.
2 - Place the front panel above the UPS.
3 - Remove the 4 fixing screws on the right
side to free the battery sub-module.
4 - Pull the battery sub-module slightly, then
lift it to extract it.

3

4

x 6

1

1

1

3

2

3

3

x 6

1

1

1

4

2

Advertising